Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Valve Characteristics – Quick Opening, Linear & Equal Percentage
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Control Valves > Valve Characteristics – Quick Opening, Linear & Equal Percentage

Valve Characteristics – Quick Opening, Linear & Equal Percentage

Last updated: July 12, 2020 12:49 pm
Editorial Staff
Control Valves
6 Comments
Share
10 Min Read
SHARE

In essence a valve simply functions as a restriction in a flow line, with flow areas A1 and A2 and pressure differential p1 – p2, as shown in Below Figure.

Contents
Valve CharacteristicsC = 40xInstalled flow characteristicTypical application of quick opening, linear and equal percentage valvesi) Quick opening valveii) Linear valveiii) Equal percentage valve (most commonly used valve)

Valve Characteristics

Valve characteristics

The below mentioned flow equation describe the flow rate of a fluid through a valve. The form of this equation used by valve suppliers is:

valve flow coefficient

where C is the valve flow coefficient, q the flow rate of the liquid through the valve, Δp = p1 – p2 the pressure difference across the valve and G the specific gravity (relative density) of the fluid.

For historical reasons, the flow rate q, in above Equation, is measured in gallons per minute (gpm) and the pressure difference Δp, in pounds per square inch (psi). Valve coefficient, C is fundamentally determined by the effective flow areas A1 and A2 of the valve.

The value of C will therefore change from zero (when the valve is fully closed) to a maximum value (when the valve is fully opened).

Assume that a valve is opened a certain amount x (with x denoting the fractional valve opening or valve travel between 0 and 1 ( 0% to 100%)).

The flow rate q, of the liquid (we will assume water with G = 1 ), flowing through the valve, is now allowed to increase until the pressure Δp across the valve, reaches a maximum of say 4 psi (assumption).

We may conceivably expect the results depicted in Below Figure, shown for x = 0 (valve fully closed), x = 0.25 (valve one quarter open), x = 0.5 (valve half open), x = 0.75 (valve three quarters open) and x = 1 (valve fully open).

Control Valve characteristic with Equation

The special value of C that corresponds to the valve fully open, is called the characteristic flow coefficient of the valve and denoted by CV.

The characteristic flow coefficient CV, is an extremely important parameter of a specific valve, and is used extensively when choosing the correct valve for a certain application.

For the valve characteristics in Above Figure, for example, CV = 40.

The way q varies when the pressure is kept constant (normally the rated pressure drop across the valve for maximum flow) and the way C changes as the valve opening x changes, may be available for a particular valve, provided by the manufacturer in tabulated format.

For example, the graph of q (with Δp = 4 psi) as a function of x and the graph of C as a function of x, are shown in Below Figures (a) and (b) respectively, for the flow characteristics of our hypothetical valve, depicted in above Figure.

Control Valve Opening Graph

The different values of C obtained as the valve travels through its full range (or stroke as it is also called) from closed to open, is generally expressed in the following format, by valve manufacturers:

C = CV×f(x)       …Equation 1

where f(x) is called the inherent valve characteristic of a particular valve. For example, from the graph of C, in Above Figure (b), we could express C as:

C = 40x

and we conclude therefore from Equation 1, that CV = 40 and f(x) = x.

The function f(x) varies from 0 (valve closed with x equal to 0) to 1 (valve fully open with x equal to 1). The inherent valve characteristic f(x), is intimately linked to the flow rate q through a valve, as we can see if we replace C with CVf(x) (as per Equation 1), to rewrite the valve Equation in the form:

valve Equation

It is indeed clear from above Equation that if we keep Δp constant (for a given liquid, G is constant as well), q and f(x) will have exactly the same shape.

A valve for which f(x) = x, is called a linear valve because the flow rate will change linearly with valve opening x. Depending however on the valve design, f(x) may also reflect quick opening or equal percentage (slow opening) characteristics, as shown in Below Figure.

Control valve characteristics

The flow behaviour of a valve is dictated by the manner in which the flow areas A1 and A2 changes with valve position and therefore by the style and design of the valve trimming and in particular the design of the valve seat and closure member (plug).

The quick opening flow characteristic provides for maximum change in flow rate at low valve travels with a nearly linear relationship. Additional increases in valve travel gives sharply reduced changes in flow rate.

The linear flow characteristic curve allows the flow rate to be directly proportional to the valve travel (Δq/Δx equals a constant) or in terms of the inherent valve characteristic, f(x) = x.

An equal percentage valve starts initially with a slow increase in flow rate with valve position which dramatically increases as the valve opens more.

The term equal percentage for a slow opening characteristic curve may at first be confused with the description of a linear characteristic curve.

However, for an equal percentage valve, Δq/Δx at any stage, is proportional to the flow rate q at that moment. This is in contrast with a linear characteristic for which Δq/Δx is constant.

That Δq/Δx is proportional to q, may be rephrased as Δq/q is proportional to Δx. This means the percentage change Δq with respect to the current flow rate q (that is (Δq/q)×100), is equal at every valve travel position x for the same change in valve travel Δx, hence the term ‘equal percentage’.

The inherent valve characteristic for an equal percentage valve is exponential in nature and is normally given by valve manufacturers in the form

Control Valve Formula

where R is a constant for the valve.

The exponential behaviour of an equal percentage valve is explored further in Below Example

An equal percentage valve delivers 8 gpm of water when the valve is 50% open (x=0.5). When the valve is 60% open (x=0.6), the flow rate increases to 16 gpm. Estimate the flow rate through the valve when it is 70% open (x=0.7).

Assume that the pressure drop across the valve remains constant.

Equal percentage valve Problems

Answer:

When the valve opens from 50% to 60%, the flow rate changes from 8 gpm to 16 gpm. This means that Δq is 8 gpm. when Δx is 0.1 and q = 8.

Therefore Δq/q = 8/8 = 1 and the percentage change is 100% (Δq/q×100) at x = 0,5.

For an equal percentage valve, the percentage change in flow rate when the valve opens from 50% to 60%, (Δx = 0.1) must be equal to the percentage change in flow rate when the valve opens from 60% to 70% (the same Δx of 0.1).

Therefore Δq/q at x = 0.6 must also be 1 (or 100%) for Δx = 0,1. But q is 16 gpm. when the valve is 60% open and we conclude that Δq should be 16 gpm. when the valve opening changes from 60% to 70%.

The flow rate through the valve is therefore approximately 32 gpm. at 70% valve opening.

Installed flow characteristic

When valves are installed with pumps, piping and fittings, and other process equipment, the pressure drop across the valve will vary as the valve travel changes.

When the actual flow in a system is plotted against valve opening, the curve is called the installed flow characteristic and it will differ from the inherent valve characteristic which assumed constant pressure drop across the valve.

When in service, a linear valve will in general resemble a quick opening valve while an equal percentage valve will in general resemble a linear valve.

Typical application of quick opening, linear and equal percentage valves

i) Quick opening valve

  • Frequent on-off service.
  • Used for systems where ‘instant’ large flow is needed (safety or cooling water systems).

ii) Linear valve

  • Liquid level and flow control loops.
  • Used in systems where the pressure drop across the valve is expected to remain fairly constant.

iii) Equal percentage valve (most commonly used valve)

  • Temperature and pressure control loops.
  • Used in systems where large changes in pressure drop across the valve are expected.

Articles You May Like :

Facts of Control Valves

Control Valves Theory

Valves Pressure Loss 

Flow Meter Verification

Control Valve Questions

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Control Valve Packing
Globe Valve Body Design
What is a 4-way Solenoid Valve?
Solenoid Valve Selection Criteria
How Ball Valves Work ?
What is Reducing Valve ?
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
6 Comments
  • Navnit patel says:
    June 16, 2016 at 5:57 am

    Provided Excellent control valves knowledge with graphics, equation,

    Reply
  • mehdi says:
    December 23, 2016 at 8:47 am

    what is your refrence article or manual or documents for your equation mentioned ?

    Reply
  • JM says:
    March 21, 2017 at 7:50 am

    Dear Sir,

    Wonderful explanation.

    I have one question about Cv mentioned on tag plate of Control Valve. As per above explanation, Cv indicates flow(Obviously max) through 100 % opened control valve having DP equal to 1(unit).
    1) How this Cv can be interpreted for any intermediate position of valve?.
    2) is it necessary to have DP across valve = to 1(unit) during normal operation?

    Thanking You.

    Reply
  • Qadir Mohtasham says:
    March 26, 2019 at 8:07 pm

    Great

    Reply
  • Raem says:
    March 5, 2020 at 2:28 pm

    Good article

    Reply
  • Donald Douthett says:
    January 12, 2021 at 6:23 pm

    I am sorry that I cannot participate in the discussion now. I don’t have the information I need. But this topic interests me very much.

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

How Valve Positioners act as Cascade Control Systems in a Loop?
What is Valve Packing ?
Valve Basics, Sizing, and Actuators Books
3 Port 2 Position Direct Acting Solenoid Valve Working Principle
Complementary Control Valve Sequence
Pneumatic Valves Questions & Answers
Self-Actuated Valves, Pneumatic & Hydraulic Actuators
What is Motor Actuator ?

Keep Learning

Control Valves Pre-Commissioning Checklist

Control Valves Pre-Commissioning Checklist

What is Pump Cavitation

What is Pump Cavitation? How to Avoid Cavitation?

Selecting the Proper Failure Mode

How to Select Control Valve Failure Mode

control valve sizing problem

Importance of Proper Control Valve Sizing

Types of Pneumatic Valves

Types of Pneumatic Valves : Poppet & Spool

Valve stem travel

Control Valves Mechanical Friction Problems

Why Restriction Orifice is some distance from Blowdown valve

Why Restriction Orifice is some distance from Blowdown valve ?

Control Valve pressure recovery

What is Control Valve Flashing ?

Learn More

Industry 4.0 Explained

Industry 4.0 Explained – Industrial Internet of Things

Chromatography Questions & Answers

Gas Solid Chromatography Questions & Answers

Three Wire RTD Circuit

What is a Three-wire RTD ?

Uncertainty Calculations of Pressure Calibration

Uncertainty Calculations of Pressure Calibration

Comparators Objective Questions

Comparators Objective Questions

Process Pressure Measurement Objective Questions

Process Pressure Measurement Objective Questions

Chemiluminescent Analyzer

Chemiluminescence

Difference Between Resistive Touch and Capacitive Touch

Difference Between Resistive Touch and Capacitive Touch

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?