Basic Steps and Procedure for the Repair of Control Valve

In this article, we will discuss the basic steps and procedure for the repair of Kent introl (KOSO) control valve.

Procedure for the Repair of Control Valve

Procedure for the Repair of Control Valve
Image Courtesy: kentintrol

The below steps mentioned the detailed step-by-step procedure for the repair of control valves.

  1. Close Upstream and downstream isolation valves of the control valve.
  2. Depressurize the line pressure by opening drain valves and flush with nitrogen.
  3. Remove all electrical and pneumatic connections to the control valve.
  4. Dismantle the control valve body, bonnet top flange along with actuator yoke.
  5. Inspect the valve internals and service the valve.
  6. Replace the damaged parts with OEM spares.
  7. Assemble the valve body and bonnet flange along with the actuator.
  8. Perform hydro test as per pressure rating of the control valve. (mentioned below)
  9. Normalize the electrical and pneumatic connections.
  10. Carry out smart valve positioner calibration and control valve stroke check.
  11. Close the drain valves.
  12. Normalize the upstream and downstream isolation valves.

Control Valve Hydro Test Procedure

Follow the below steps to carry out the hydro-test of a control valve.

  1. Remove the valve from the process line.
  2. Connect blinded flange in the control valve (c/v) outlet.
  3. Connect threaded flange in the c/v inlet.
  4. Connect Haskel pump set up in the inlet.
  5. Keep control valve at full open position.
  6. Using haskel pump, pressurize control valve body with water at 225Kg/cm2.
  7. Isolate the haskel pump set up and check for any leakages for 15 minutes.
  8. Depressurize the pressure in the valve body.
  9. Connect the valve back into process line.

Note:

  1. The haskel pump uses instrument air to operate and generates very high-pressure output. You can use any other available high-pressure pump for testing purposes.
  2. The specifications of control valves depends as per your installed base in your plant.

Credits: PLQP Instrumentation Team

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago