#8 PLC Best Practices – Validate HMI Input Variables at PLC Level

HMI access to PLC variables can (and should) be restricted to a valid operational value range at the HMI, but further cross-checks in the PLC should be added to prevent, or alert on, values outside of the acceptable ranges which are programmed into the HMI.

Security ObjectiveTarget Group
The integrity of PLC variablesProduct Supplier Integration / Maintenance Service Provider

Validate HMI Input Variables at PLC Level

Input validation could include out-of-bounds checks for valid operational values as well as valid values in terms of data types that are relative to the process.

If a PLC variable receives a value that is out-of-bounds, provide PLC logic to either input a default value to that variable which does not negatively affect the process, and can be used as a flag for alerts, or input the last correct value to that value and log the event for further analysis.

HMI screen for operator

Example 1

An operation requires a user to input a value on an HMI for valve pressure. Valid ranges for this operation are 0-100, and the user’s input is passed from the user input function on the HMI to the V1 variable in the PLC.

In this case,

  1. HMI input to variable V1 has a restricted range of 0-100 (dec.) programmed into the HMI.

2. The PLC has a cross-check logic that states:

IF V1 < 0 OR IF V1 > 100, SET V1 = 0.

This provides a positive response of a presumably safe value to an invalid input to that variable.

Example 2

An operation requires user input for measurement thresholds to a variable that should always be within an INT2 data range. The user input is passed from the HMI into the V2 variable in the PLC, which is a 16-bit data register.

  1. HMI input to variable V2 has a restricted range of -32768 to 32767 (dec.) programmed into the HMI.

2. The PLC has data-type cross-check logic that monitors the overflow variable (V3), which exists just after V2 in the PLC’s memory structure:

IF V2 = -32768 OR IF V2 = 32767 AND V3 != 0,

SET V2 = 0 AND SET V3 = 0 AND SET DataTypeOverflowAlarm = TRUE.

Example 3

Scale PV (Process Value), SP (SetPoint), and CV (Control Variable) for PID (Proportional, Integral, Derivative controller) to consistent or raw units to eliminate scaling errors causing control problems.

Incorrect scaling might lead to inadvertent abuse cases.

Why?

Beneficial for…?Why?
                    Security1. While HMIs typically provide some sort of input validation, a malicious actor can craft or replay modified packets to send arbitrary values to the variables in the PLC which are open to outside influence (open to values passed from an HMI, for example).

2. PLC protocols are typically marketed as “open” protocols and published to the general public, so creating malware that utilizes “open” protocol information can be trivial to develop.

PLC variable mapping can typically occur through traffic analysis during the reconnaissance phases of an attack, thus providing the intruder with the necessary information to craft malicious traffic to the target and thereby manipulate a process with unauthorized tools.

Cross-checking values passed into the PLC before implementing that data into the process ensures valid data ranges and mitigates an invalid value in those memory locations by forcibly setting safe ranges when a value is detected as out-of-bounds during the course of the PLC scan.
Reliability/
Maintenance/

References

Standard/frameworkMapping
MITRE ATT&CK for ICSTactic: TA010 – Impair Process Control
Technique: T0836 – Modify Parameter
ISA 62443-3-3SR 3.5: Input Validation
SR 3.6: Deterministic Output
ISA 62443-4-2CR 3.5: Input Validation
CR 3.6: Deterministic Output
ISA 62443-4-1SI-2: Secure coding standards
SVV-1: Security requirements testing
MITRE CWECWE-1320: Improper Protection for Out of Bounds Signal Level Alerts

Source: PLC Security

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago