Liquid Level Switch Control Pump and Lamp

This pictorial diagram shows how a liquid level switch (with two separate SPDT switch units actuated by a common float mechanism) is wired to control both an electric pump and a lamp:

Liquid Level Switch

Liquid Level Switch Control Pump and Lamp

Under what liquid level condition will the lamp energize?

Under what liquid level condition will the pump motor energize?

Determine what an AC voltmeter would register under the following conditions:

→ Connected between terminals 1 and 2; high liquid level

→ Connected between terminals 2 and 6; low liquid level

→ Connected between terminals 4 and 7; low liquid level

→ Connected between terminals 1 and 6; high liquid level

Supposing the pump motor refused to energize but the lamp still functioned properly (turning on and off when it should), devise a series of diagnostic tests you could implement with an AC voltmeter to locate the fault. For each test, explain what the result of that test means for your diagnosis of the problem.

Solution:

The lamp receives power through an NC (normally-closed) switch contact, which means it will be energized when the level switch is in the resting (low level) state.

The pump motor receives power through a NO (normally-open) switch contact, which means it will be energized when the level switch is in the actuated (high level) state.

Determine what an AC voltmeter would register under the following conditions:

→ Connected between terminals 1 and 2; high liquid level – 120 VAC regardless of the level

→ Connected between terminals 2 and 6; low liquid level – 0 VAC

→ Connected between terminals 4 and 7; low liquid level – 120 VAC

→ Connected between terminals 1 and 6; high liquid level – 0 VAC

The symptoms tell us the problem must be limited to the pump circuit, and cannot be related to anything common with both the pump and lamp because the lamp still works as it should.

Taking a voltage measurement between terminals 6 and 7 while the liquid is at a high level is a good first step: the presence of 120 VAC between those points would indicate the switch is closing at it should, and that there must be an open fault between those terminals and the motor (including possibly within the motor itself ).

The lack of voltage between those points during a high liquid level would indicate an open fault between those terminals the source.

Here are some indeterminate tests. For each one, challenge engineers to explain why the specified test would not give good diagnostic information:

Measuring voltage between terminals 1 and 2 (We already know there is the supply voltage, since the lamp works)

Measuring voltage between terminals 6 and 7 while the liquid level is low (it is impossible for any fault prohibiting motor function to yield anything but zero volts in a condition of low level, and therefore this test tells us nothing about the problem).

Credits: Tony R. Kuphaldt

Read Next:

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Network Switch Requirement in SCADA and DCS Architecture

In this post, we will learn the basic requirements for a network switch to be…

3 days ago
  • PLC Tutorials

PLC Panel and MCC Panel Interface Signals

The PLC panel and MCC panel interface signals are start, stop, run feedback, trip, local…

5 days ago
  • PLC Tutorials

Shutter Door Control using Motor and Limit Switches

 In this article, we are going to discuss about shutter door control using induction motor…

1 week ago
  • Electrical Basics

Electrical Drives – Modes, Types, Speed Control Applications

Electrical Drives control the motion of electric motors. Motion control is required in industrial and…

1 week ago
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

1 week ago