Root Cause Analysis (RCA)

High-pressure Service Level Transmitters Misunderstood Zero Drifts

Instrumentation engineering root cause analysis of high-pressure service displacer level transmitter zero drifts problems.

Article Type:Root Cause Analysis (RCA)
Category:Instrumentation
Equipment Type:Sensors
Author:S. Raghava Chari

Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of two or three decades ago. These articles will help you to improve your troubleshooting skills and knowledge.

Level Transmitters Zero Drifts Problem

Operating crew constantly complained about 250 bars pressure vessels Displacer Level Transmitters showing below zero readings in plant shutdown and de-pressured conditions.

Author solution

The author thought over the problem and realized that the running conditions vessel synthesis gas pressure is 250 bars; its density at that pressure is 162 Kg/m3. It is comparable to the below the gas-liquid ammonia density of 640 Kg/m3.

The crew adjusts the zero for this condition. On the other hand, the vessel pressure is zero under shutdown conditions and gas/air fill density is negligible.

Hence, the displacer loses no weight. Since, the more weight the displacer loses the higher the displacer level transmitter (DLT) output, the weight not losing displacer level transmitter (DLT) reads below zero during de-pressured conditions. This is right and best left as is.

Benefits Realized

Realized benefits are:

  1. Vanished frivolous work orders and efforts spent on it in making a correct reading wrong!
  2. Consequent erroneous readings during normal run generated wrong data which could mislead troubleshooters

Author: S. Raghava Chari

Do you face any similar issues? Share with us through the below comments section.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !
Share

Recent Articles

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

7 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago