Fire & Gas System

Gas Detectors Practical Problems and Troubleshooting

Gas detectors are one of the most important safety devices used in plants. Gas detectors are of various types and available for detection of various gases like Chlorine gas, hydrogen sulphide gas, carbon monoxide gas and many other gases.

Many times, we encounter problems with these gas detectors and face issues in troubleshooting of these gas detectors.

Gas Detectors Practical Problems

Gas Detectors Practical Problems and Troubleshooting

Below mentioned steps can be followed for troubleshooting the problems in any gas detector.

  1. For gas detector not responding, check the display of the gas detector. If the display is in power off condition, then check the voltage to the gas detector. If no voltage is present, then check the fuse in marshalling cabinet. If fuse is ok, then check the barrier or the isolator’s healthiness in the marshalling cabinet. If found ok, then check the cable connections in field, junction box and in marshalling cabinet. If connections are ok, then check the healthiness of the cable. Check the resistance of the cable to know the healthiness of the cable. If the cable is found faulty, then reply the pair with a spare pair.
  2. Still if gas detector is not getting on, then check the connection in the terminal block of the gas detector. The connections in the gas detector’s terminal block can be incorrect. Use the vendor manual for confirming the connections. Most of the gas detectors are 3 wire. Hence checking connections is necessary.
  3. Check the sensor’s sintered filter. The filter might be blocked by external dust or dirt. Clean the filter with a proper tool like a brush or moisture free air. Also check the condition of the sensor. If dust or dirt is present on sensor, then clean the sensor also. Reinstall the sensor and sintered filter. Check the response with the calibration gas.
  4. If gas detector is not responding then check the connections of the sensor to the terminal block. Loose connection or incorrect connection can create such problem.
  5. If the gas detector is showing non zero reading when there is no leakage or gas present, then power reboot the gas detector.
  6. If still the gas detector is showing values, then calibration of gas detector is needed. Use appropriate gas for calibration of the gas detector.
  7. If above mentioned steps do not solve the issue, then replace the sensor. Check the removed sensor’s response with another transmitter.
  8. If replacing sensor doesn’t work then replace the transmitter. Use old sensor if the response of the sensor is ok with another transmitter.
You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago