Suppose this Fisher model 546 I/P transducer has an input range of 4-20 mA and an output range of 3-15 PSI:
Note: This is an old model, now many smart I/P converters available n the market.
Identify which way the magnetic shunt would have to be moved in order to re-calibrate the I/P transducer to a new output range of 4-20 PSI (from 3-15 PSI), explaining your reasoning.
Identify which way the zero screw would have to be turned in order to re-calibrate the I/P transducer to a new output range of 2-14 PSI (from 3-15 PSI), explaining your reasoning.
Answer:
Move the magnetic shunt further out in order to re-calibrate from 3-15 PSI to 4-20 PSI.
Turn the zero screw so the spring doesn’t push down as hard on the right-hand side of the beam in order to re-calibrate from 3-15 PSI to 2-14 PSI.
1. What would happen if some of the turns in the electromagnet coil were shorted past? Would this cause a zero shift, a span shift, or a linearity shift?
2. What would happen if the zero spring broke into two separate pieces? Would this cause a zero shift, a span shift, or a linearity shift?
3. Suppose this I/P outputs a pressure of 9.0 PSI at an input current of 12.3 mA. Calculate the error, in percent of span.
4. Suppose this I/P outputs a pressure of 12.5 PSI at an input current of 16.0 mA. Calculate the error, in percent of span.
5. Suppose this I/P outputs a pressure of 5.7 PSI at an input current of 8.0 mA. Calculate the error, in percent of span.
Share your answers with us through the below comments section.
Credits: Tony R. Kuphaldt
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…