Instrumentation engineering root cause analysis of erratic reading of H2 flow rotameter.
Article Type: | Root Cause Analysis (RCA) |
Category: | Instrumentation |
Equipment Type: | Sensors |
Author: | S. Raghava Chari |
Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of two or three decades ago. These articles will help you to improve your troubleshooting skills and knowledge.
Erratic H2 flow rotameter readings prevented newly charged catalyst reduction and delayed Reformed Gas Production.
The instrument crew complained about the pipe fitter’s inability to make the ¾ pipe exactly vertical. Hence, stuck rotameter float and unreliable readings
They too expressed the near impossibility of the slender ¾” pipeline ‘rotameter plumb’. Even if they achieve it, it does not stay that way!
He told the Instrument crew to do the following:
Problems vanished and reformer started smoothly.
Author: S. Raghava Chari
Do you face any similar issues? Share with us through the below comments section.
If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
PLC ladder logic design to control 3 motors with toggle switch and explain the program…
VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…