Emergency Stop Switch Spurious Trip

Today we will discuss about one of the most important components used in the Instrumentation system i.e. NC contact. This is widely used in Emergency Stop or Stop pushbutton as a fail-safe condition is needed there.

Emergency Stop Switch Spurious Trip

NC Contact with Push button

This system may lead to spurious trips in long run. Yes, you read it right SPURIOUS TRIP!

Internal Components of Switch

The switch Normally-Close (NC) contact used has a simple internal as shown below. The main components are spring and contact in a switch.

Now as per the fail-safe concept, the stop button contact should be closed in non-actuated conditions for many hours and days as per the required application. Whenever the pushbutton is pressed, which is maintained mainly by a spring and contact, the contact should open.

Now due to the aging effect, this spring may fail or its strength may be lost after some time. Sometimes these issues may create an open contact and actuate the pushbutton without actually pressing the stop button, which is a SPURIOUS TRIP.

Problem Solution

To avoid these types of problems, 2 out of 2 configurations should be used. For this, 2 sets of contacts in a single pushbutton must be used in place of 1 set of contact of the Normally-closed push button.

Whenever both contacts are actuated then only, stop/trip action should take place i.e. both contacts should be connected in parallel.

If the switch contacts are taken as Digital Input in PLC or DCS logic, then 2 different DI should be used so that the health of both pushbuttons can be monitored in the logic, i.e. alarm should appear whenever a contact is actuated such that respective action can be configured in the logic.

How to Check Switch Contact Status?

In non-actuated conditions (for NC contact), resistance should be below 1 ohm, while in the actuated condition it should give resistance in mega Ohm.

When to Check Switch Contact healthiness?

We have to check the switch contact healthiness every 3 years or during a major plant shutdown.

If your plant has any specific control philosophy then you have to follow the recommended documents or standards.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

  • The 'aging" causing the effect of having spurious trip with the switch opening the contacts (Normally closed), will it be a permanent spring failure? or can it be that the spring work normally after the spurious trip? Should we recommend a switch / pushbutton / relay with two set of NC contacts? thanks

Share

Recent Articles

  • PLC Tutorials

Shutter Door Control using Motor and Limit Switches

 In this article, we are going to discuss about shutter door control using induction motor…

5 days ago
  • Electrical Basics

Electrical Drives – Modes, Types, Speed Control Applications

Electrical Drives control the motion of electric motors. Motion control is required in industrial and…

5 days ago
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

5 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

1 week ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

1 week ago