DP Level Transmitter Elevation and Suppression Corrections

DP Transmitter Elevation and Suppression Corrections for Level Measurement

When installing a DP transmitter to measure liquid level, configuration of the transmitter often must include an adjustment for one of two conditions introduced by the mounting arrangement.

Elevated Span

The Lower Range Value (LRV) of the transmitter needs to be configured above “0.”

Suppressed Span

The LRV of the transmitter needs to be configured below “0.”

Elevated Span and Suppressed Span

A brief discussion of how to make adjustments for elevation and suppression follows. Then two examples of the calculations needed to determine configuration parameters are given. Finally, a brief procedure that does not involve calculations is provided.

The range of the transmitter can be set anywhere, forward or reverse acting, as long as the following criteria are met:

LRL ≤ LRV ≤ URL
LRL ≤ URV ≤ URL

Span = [URV – LRV] ≥ Min Span

Note that the URL (Upper Range Limit), LRL (Lower Range Limit), and Min Span are transmitter dependent.

Transmitter Elevation Calculation Example

The below figure shows a sample transmitter installation.

1. Calculate the differential pressure as follows.

Pressure@DP = (H × SpG)High Side – (H × SpG)Low Side

where H = Height

2. Calculate the LRV when the tank is empty.

LRV = (120 x 1.0)High Side – (0 x 1.0)Low Side

LRV = +120 inH2O

3. Calculate the URV.

URV = LRV + Span
URV = +120 + 100
URV = 220 inH2O

Therefore, transmitter range should be 120 to 220 inH2O

Transmitter Suppression Calculation Example

The below figure shows a sample transmitter installation.

1. Calculate the differential pressure as follows.

Pressure@DP = (H × SpG)High Side – (H × SpG)Low Side

where H = Height

2. Calculate the LRV when the tank is empty.

LRV = (0 x 1.0)High Side – (100 x 1.0)Low Side

LRV = -100 inH2O

3. Calculate the URV.

URV = LRV + Span
URV = -100 + 100
URV = 0 inH2O

Therefore, transmitter range should be -100 to 0 inH2O

Source : Siemens Pressure Transmitter

Articles You May Like :

Closed Tank Remote Seal Capillary

Tank Interface Level Measurement

Process Variable to Percentage

Valve Pressure Drop Calculation

Transmitter Output in Percentage

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

4 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

1 day ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago