Calculate the proper LRV and URV pressures for the 4-20 mA loop-powered DP transmitter in this level measurement scenario:
Then, calculate the transmitter’s output given the following process levels (assuming perfect transmitter calibration):
Output = mA with the kerosene level 4 feet up from the bottom of the tank (4 feet “fillage”)
Output = mA with the kerosene level 6 feet down from the top of the tank (6 feet “ullage”)
Answer:
Note: a weight density (γ) of 51.2 lb/ft3 is assumed for kerosene.
LRV = 56.62 ”WC = 2.046 PSI
URV = 164.9 ”WC = 5.959 PSI
Output = 5.455 mA with the kerosene level 4 feet up from the bottom of the tank (4 feet “fillage”)
Output = 12.73 mA with the kerosene level 6 feet down from the top of the tank (6 feet “ullage”)
More Questions
1. Suppose the DP transmitter with the remote seal failed and had to be replaced. Unfortunately, you don’t have another DP transmitter with a remote seal in stock to replace it. Could you use a DP transmitter without a remote seal for this application? If so, would its calibration have to be different from the remote-seal transmitter?
2. Explain why this installation does not require a compensating leg.
Share your answers with us through the below comments section.
Read Next:
Credits: Tony R. Kuphaldt
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…
This article explains how to blink lights in ladder logic with a detailed explanation video…