Air Compressor Control Circuit Problem

This air compressor control circuit has a problem. The air compressor refuses to start even when the air pressure is zero PSI.

Air Compressor Control Circuit

Air Compressor Control Circuit has a Problem

A technician begins diagnosing the circuit, following the steps shown (in order):

Test 1: Measured 120 VAC between points A and C, with “Hand/Off/Auto” switch in the “Auto” position.

Test 2: Measured 120 VAC between points A and D, with “Hand/Off/Auto” switch in “Auto” position.

Test 3: Measured 0 VAC between points E and C, with “Hand/Off/Auto” switch in “Auto” position.

Test 4: Jumpered points A and B, with “Hand/Off/Auto” switch in “Auto” position. The motor did not start.

Identify any useful information about the nature or location of the fault derived from the results of each test, in order of the tests performed. If the test is not useful (i.e. provides no new information), mark it as such.

Assuming there is only one fault in the circuit, identify the location and nature of the fault as precisely as you can from the test results shown above.

Answer:

Test 1: Measured 120 VAC between points A and C, with “Hand/Off/Auto” switch in the “Auto” position. Proves there is 120 VAC control power available, that the fuse is good, and that the Hand/Off/Auto switch is passing power through to point A.

Test 2: Measured 120 VAC between points A and D, with “Hand/Off/Auto” switch in “Auto” position. Proves there is an “open” fault somewhere between those points, in one of the two switches, and that we do not have any other “open” faults in the contactor coil circuit.

Test 3: Measured 0 VAC between points E and C, with “Hand/Off/Auto” switch in “Auto” position. This is an unnecessary test, as we already know there is continuity through the overload contact.

Test 4: Jumpered points A and B, with “Hand/Off/Auto” switch in “Auto” position. The motor did not start. Combined with the results of previous tests, this test proves the “open” fault must lie between points B and D: namely the PSH.

The fault is an “open” high pressure switch (PSH), or in the wires connecting the PSH to points B and D.

Share your answers with us through the below comments section.

Read Next:

Credits: Tony R. Kuphaldt

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

2 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

2 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

2 weeks ago
  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

3 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

1 month ago