Reading: Digital Control Valve (DCV) Calibration Procedure
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Guest Articles > Digital Control Valve (DCV) Calibration Procedure

Digital Control Valve (DCV) Calibration Procedure

Last updated: December 22, 2018 12:18 am
Editorial Staff
Guest Articles
No Comments
Share
3 Min Read
SHARE

CALIBRATION PROCEDURE FOR DIGITAL CONTROL VALVE 

The below calibration procedure for Digital Control Valve. Make : Fisher, Model :  DVC 6000

Also Read : Digital Control Valve Principle

Tools Required:

1. 375 Field communicator
2. Tools kit
3. DATA sheet

Calibration Procedure

  1. Take the work permit from shift in-charge
  2. Checking for valve accessories any damage for DVC feed back, guage, air regulator and filter
  3. Check the pressure regulator guage and set it according to bench set
  4. Check the positioner cam alignment ,cam alignment should be matched with travel length
  5. Operate the valve from DCS, observe the valve travelling condition , if it is not matching with our requirement then we have to connect the 375 field communicator at positioner terminal ( ie. Loop + and -)
  6. Switch on the communicator then select FF application in Communicator.
  7. Select required tag number from list ,then select transducer block and select configuration setup
  8. Again click basic setup enter in to setup wizard, transducer go to manual mode for performing setup
  9. As per data sheet , check the data’s whether it is matching or not
    a) Travel length
    b) Check the pressure unit (psi or kg/cm2)
    c) Check actuator manufacture and model number and actuator size
  10. Now we will go for auto calibration standard than select manual crossover adjustment
  11.  Then check visually whether feedback arm is matching with the hole of the DVC body or not?
  12. Run performance tuner and check the valve operation
  13. Calibration over than change the valve auto mode
  14. Check for valve stroke after auto calibration from DCS

TroubleShooting:

  • If Valve hunting is vigorously
    a) Go to detail setup
    b) Go to response control
    c) Click travel tuning

For fisher control valve adjust travel tuning set to lower alphabet ( If setting was D we have to select C).

For other valves we have adjust proportional gain

  • If Valve is over shooting
    a) Go to detail setup
    b) Go to response control
    c) Click pressure tuning

For fisher control valve adjust pressure tuning set to lower alphabet ( If setting was D we have to select C).

For other valves we have adjust proportional gain

NOTE:

Relay – A = Double Acting
Relay –B = Reverse acting
Relay –C = Forward & Reverse acting

Article by
Vamsi
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Difference between PT100, PT1000, Nickel RTD and Balco RTD
5 Tips to Pass CFSE Exam
Capacitance Level Switch Calibration
Oracle Database 12c Administrator Certified Associate Certification
Safety Switches for Controlling Conveyor Operations
Control Valve Cavitation and Flashing
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Redundant Power Supply for Critical Field Panels
Colleges to Study Instrumentation Engineering in United States
Open Tank DP Level Transmitter Calculations
PLC Program for Latching and unlatching Circuit
PLC Program for Automatic Bottle Rejection System
Internal Powered Modems
Pros and Cons of Online Courses
DP Transmitter Dry Leg & Wet Leg Calculations

Keep Learning

Automatic Lamp Control in Storage Facility

PLC Program for Automatic Lamp Control in Storage Facility

Cable Glands

Using of MCT instead of Cable Glands on the Cabinets

PLC Program for Car Parking

PLC Program for Entry and Exit Control of Car Parking

Abbreviations of Pressure, Temperature & Flow

Abbreviations of Pressure, Temperature & Flow

PLC Program for Conditional Control Logic

PLC Program for Conditional Control Logic

Microsoft MS-200 certification

Best Preparation Tool You Can Get Online for Microsoft MS-200

PLC Program for Automatic Parameter initialization

PLC Program for Automatic Parameter Initialization When Power UP

RJ45 Connector Pins

How to make RJ45 cable

Learn More

Advantages of Three Phase System Compared to Single Phase System

Advantages of Three Phase System Compared to Single Phase System

Instrumentation loop Diagram

Instrumentation Loop Diagrams

Basics of Motion Controllers

Basics of Motion Controllers

PLC based Automatic Bell System

PLC based Automatic Bell System for a School

bimetallic thermometer working principle

Different Types of Thermometers

Electron Flow Through Battery

Batteries Theory

Distributed Control System Interview Questions

PLC Program for Analog Input Sampling

PLC Analog Input Sampling Ladder Logic

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?