The Transit Time flow meter measures the time it takes for an ultrasonic signal transmitted from one transducer to cross a pipe and be received by a second transducer.
Upstream and downstream time measurements are compared. With no flow, the transit time would be equal in both directions.
With flow, sound will travel faster in the direction of flow and slower against the flow.
Very accurate timing circuits are required but 1% accuracy is quite typical when the transducers can be mounted on a pipe section with evenly distributed flow.
Because the ultrasonic signal must cross the pipe to a receiving transducer, the fluid must not contain a significant concentration of bubbles or solids (less than 2%).
Otherwise, the high-frequency sound will be attenuated and too weak to traverse the pipe.
Applications include potable water, cooling water, water/glycol solutions, hydraulic oil, fuel oils, and chemicals.
Transit Time transducers typically operate in the 1-2 MHz frequencies. Higher frequency designs are normally used in smaller pipes and lower frequencies for large pipes up to several meters in diameter.
Source: Greyline Instruments
If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
Electrical Drives control the motion of electric motors. Motion control is required in industrial and…
PLC ladder logic design to control 3 motors with toggle switch and explain the program…
VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…