Practical Questions

Solenoid Valves Questions & Answers – 2

Solenoid valve SV-92 plays an important role in this compressor inlet separator control system. Level control valve LV-92 opens up when needed to drain liquid out of the “boot” of the separator vessel, which ideally contains only gas (vapor).

Examine this P&ID and then answer the following questions:

compressor emergency shutdown system

Questions :

  1. Identify the statuses of SV-92 and LV-92 when the separator boot liquid level is at or below the normal level of 1 foot 4 inches.
  2. Describe how this system responds to high liquid levels in the separator boot.
  3. What will be the consequence of an instrument air supply failure, as it relates to the separator boot liquid level?
  4. What will be the consequence of an AC power failure to LIC-92?

Answers :

  1. Identify the statuses of SV-92 and LV-92 when the separator boot liquid level is at or below the normal level of 1 foot 4 inches. LV-92 will be closed, and SV-92’s coil will be de-energized.
  2. Describe how this system responds to high liquid levels in the separator boot. If LT-92 senses a high liquid level, controller LIC-92 will respond by applying electrical power to SV-92. When SV-92 actuates, it sends instrument air to the diaphragm actuator of LV-92 to cause that drain valve to open. As LV-92 drains liquid out of the boot, the level sensed by LT-92 decreases over time, eventually to a point where controller LIC-92 stops sending power to the coil of SV-92.
  3. What will be the consequence of an instrument air supply failure, as it relates to the separator boot liquid level? Without instrument air supply (IAS), the level drain valve LV-92 can never open and the separator boot liquid level will rise unabated. Eventually LSHH-231 will detect the high-high level condition and command the Emergency Shut-Down (ESD) system to turn the compressor off in order to avoid damaging that machine.
  4. What will be the consequence of an AC power failure to LIC-92? Without AC power to energized the coil of solenoid SV-92, the level drain valve LV-92 will never be commanded to open by SV-92 and the separator boot liquid level will rise unabated. Eventually LSHH-231 will detect the high-high level condition and command the Emergency Shut-Down (ESD) system to turn the compressor off in order to avoid damaging that machine

Read All SOV Questions & Answers

Solenoid Valves Questions & Answers – 1
Solenoid Valves Questions & Answers – 2
Solenoid Valves Questions & Answers – 3
Solenoid Valves Questions & Answers – 4
Solenoid Valves Questions & Answers – 5
Solenoid Valves Questions & Answers – 6
Solenoid Valves Questions & Answers – 7

 

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

6 days ago