Pneumatic Level Transmitter Value Struck?

Suppose a level measurement system is “stuck” at one measurement value of approximately 40% even when the process liquid level rises and falls between 20% and 80% of range (as indicated by the sight-glass):

Pneumatic Level Transmitter

Pneumatic Level Transmitter Value Struck

Note: Pneumatic level transmitters were obsolete and no more found in industries.

An instrument technician removes the cover from the pneumatic transmitter and momentarily presses the baffle against the nozzle. The level indicator in the control room does not respond at all but remains fixed at about 40%.

Identify the likelihood of each possible fault in this list shown in the below table – whether the fault is “probable” (worth considering as a cause of this system’s trouble) or is “unlikely” (either completely ruled out as a cause, or just not worth considering at this point in the diagnosis) – following the results of the technician’s test:

Identify the below list of faults probable or unlikely to occur.

  1. Plugged isolation valve
  2. Plugged equalizing valve
  3. Fill fluid lost in “wet” leg
  4. Low supply air pressure
  5. Transmitter restrictor (orifice) clogged
  6. Indicator pointer stuck
  7. Transmitter nozzle clogged
  8. 3-15 PSI signal tubing plugged
  9. Transmitter out of calibration

Share your answers and explanation with us through the below comments section.

Read Next:

Credits: Tony R. Kuphaldt

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago