For any unit conversion on any PLC, you can use four function math with the following for PLC Analog Input Conversion Formula, which assumes integer math, as follows :
Formulas:
DataOffset = Data in input register at 4 mA (or zero analog signal of whatever range – for example 0 VDC on a 0-10 VDC transmitter)
DataSPan = Data at 20 mA – Data @ 4 mA
FACTOR = arbitrary factor (multiple of 10) needed to get proper resolution and accuracy
EU = Engineering Units x FACTOR
EUOffset = Engineering Units @ 4 mA x FACTOR
EUSpan = (Engineering Units @ 20 mA – Engineering Units @ 4 mA) x FACTOR
DATA = Actual data reading in input register
Note: PLC raw counts may vary from system to system.
0-60 psig from 4-20 mA with resolution of 0.1 psig:
FACTOR = 10
Data @ 4 mA = 6240
Data @ 20 mA = 31208
DataOffset = 6240
DataSpan = 31208 – 6240 = 24968
EUOffset = 0 x 10 = 0
EUSpan = (60 – 0) x 10 = 600
DATA = 18975
EU = ((EUSpan x (DATA – DataOffset))/DataSpan) + EUOffset
EU = ((600 x (18975 – 6240)) / 24968) + 0 = 306
ProcessValue = EU / FACTOR
Process Value = 306 / 10 = 30.6 psig
If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
Analyze a Cascade Control Loop
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…
In this article, you will learn the PLC programming example on timers function block using…
View Comments
NICE ONE SIR,
I APPRECIATE THIS
thank you so much sir..Its a very useful things..your work is really very good..