Closed tank DP Level Transmitter with wet leg Zero elevation Calibration |
Formulas:
Min range = – SG . H
Max range = – SG . (H-X)
Example:
If the height of an X is 2 meters and height H is 2.5 meters, there is fluid in the tank which has a density of 1 g / cm3, what is the range of calibration on the Trasmitter?
SG = 1
Min range = – 1 x (2.5 – 0)
= – 1 x 2,5 m
= – 2.5 mH 2 O
Max range = -1 X (2.5 – 2)
= -1 X 0.5 m
= -0.5 MH 2 O
The Transmitter Range = -2.5 to -0.5 mH 2 O