Categories: Control Valves

Control Valve Tips and Tricks

Discuss about Control Valve Tips and Tricks, Troubleshooting a Control Valve, Problems of Valves, Industrial Process Control Valves.

Control Valve Tips and Tricks

Control Valve Tips and Tricks

The below are the few tips and tricks on control valves:

1. If you are dealing with a corrosive fluid, choose the valve body and trim material to match the pump casing and impeller.

2. Velocity is the key to handling abrasive materials. Normal city water velocity is about 7 to 10 F.P.S. (clean liquid). If you have a fluid that is abrasive, keep the velocity as low as possible – without having the particles drop out of suspension.

3. Always sense pressure where you want to control it. Many control valves and pressure regulators do not function properly simply because they are sensing pressure at one point and being asked to control it somewhere else.

4. Velocity is the key to handling noise. Noise is energy. When dealing with high pressure drop situations try always to keep the velocities below 0.3 mach. on the inlet pipe, valve body, and outlet pipe.

5. If you use a transducer in a control loop, specify a positioner on the valve. Otherwise the transducer will rob the actuator of available thrust, and the valve will leak when it is supposed to shut off.

6. In cavitating fluids – even if the control valve has cavitation trim in it – be sure to allow a straight run of downstream pipe after the valve. If there is a pipe “T”or elbow immediately downstream, the flow will choke out and back up into the valve.

7. If you use a control valve with a bellows seal in it, try to size the valve so that its normal throttling position is near the bellows “at rest” position. This will minimize wear on the bellows.

8. Don’t use a valve below 10% of flow if at all possible. Even though a valve may have good rangeability, if the valve is used in an abrasive or erosive service (steam), it will not hold up unless it has hardened trim.

9. If a PLC is being used to control the valves in a system, specify the valves with a linear flow characteristic.

10. If a control valve is started up and fails to respond – or goes to full open or full closed and stays there – check the controller and reverse the controller’s action.

Troubleshooting a Control Valve :

1. Start with the fail mode of the valve.

If the valve fails closed and is leaking…

a) Disconnect the positioner or controller input.

b) If the valve has a hand wheel, check to see that it is backed out.

c) Check to see if the bench range is correct.

d) Check to see if there is trash in, or damage to, the valve seat.

2. Next check the positioner.

3. Next check the controller.

Do not rely on the control room to generate signals. Generate your own with equipment that you know is properly calibrated. Do not assume anything.

Remember that control valves only do what you tell them to. Many control valve problems turn out to be a problem somewhere else.

If you have any query on above or control valves, please write to me in comments.

Articles You May Like :

Questions on Control Valves

Control Valve Animation

What is a Disc Valve ?

Valve flow coefficient

What is JT Valve ?

You've successfully subscribed !

View Comments

    • Control valve hunting is when valve closes and opens at an uncontrolled rate, this could damage the packing of the valve which could cause a leak. It is not desirable and can be controlled by tuning the PID controller.

  • BY THE PID TUNING WE CAN AVOIDE THE CONTRIL WALL HUNTING (DAMPING ). HERE THE TUNING PERAMETARS ARE
    1 RATE
    2RESET
    3 GAIN
    BY ARRANGING THREE VALES WE CAN CONTROL THE CONTROL VALVE HUNTING

  • Hello,

    Having a valve on the NKOSSA site with a Fisher brand DVC6200 HC positioner, can you tell us how to set the valve position feedback please?

    NB :Thanks for your feedback.

Share

Recent Articles

  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

4 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago