Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Foundation Fieldbus (FF) Segment Topology
Share
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Communication > Foundation Fieldbus (FF) Segment Topology

Foundation Fieldbus (FF) Segment Topology

Last updated: December 16, 2019 3:39 pm
Editorial Staff
Communication
1 Comment
Share
6 Min Read
SHARE

A minimal FF H1 segment consists of a DC power supply, a “power conditioner,” exactly two terminator resistors (Note 1) (one at each extreme end of the cable), a shielded and twisted-pair cable, and of course at least two FF instruments to communicate with each other.

Contents
Foundation Fieldbus TopologyFieldbus Daisy-Chain TopologyFieldbus Bus TopologyFieldbus Tree Topology

The cable connecting each instrument to the nearest junction is called a spur (or sometimes a stub or a drop), while the cable connecting all junctions to the main power source (where a host DCS would typically be located) is called a trunk (or sometimes a home run for the section leading directly to a host system):

Note 1 : Each FF terminator resistor is actually a series resistor/capacitor network. The capacitor blocks direct current, so that the 100 resistor does not impose a DC load on the system. The substantial current that would be drawn by a 100 ohm resistor across 24 VDC source if not blocked by a series capacitor (24 V / 100 ohms = 240 mA) would not only waste power (nearly 6 watts per resistor!) but that much current would cause an unnecessary degradation of supply voltage at the field device terminals due to voltage drop along the length of the segment cable’s conductors.

Foundation Fieldbus Topology

Foundation Fieldbus Segment Topology

The power conditioner shown in this diagram is a simplified model of the actual device, the function of which being to filter out digital data pulses from reaching the DC power supply. Commercially-available Fieldbus power conditioners are complex electronic circuits rather than passive filter networks.

Normally, we would find more than two FF devices connected to a trunk cable, as well as a “host” system such as a DCS FF card for accessing FF instrument data, performing maintenance tasks, and integrating with other control loops.

Regardless of how many (or how few) FF devices connect to an H1 segment, though, there should always be exactly two terminating resistors in each segment – one at each end (Note 2) of the trunk cable. These resistor/capacitor networks serve the sole purpose of eliminating signal reflections off the ends of the trunk cable, making the cable look infinitely long from the perspective of the propagating pulse signals.

Missing terminators will result in signal reflections off the unterminated line end(s), while extra terminators have the equally deleterious effect of attenuating signal strength (as well as potentially causing signal reflections of opposite phase).

Note 2 : Be sure to check the specifications of the host system H1 interface card, because many are equipped with internal terminating resistors given the expectation that the host system will connect to one far end of the trunk!

All H1 networks are essentially parallel electrical circuits, where the two connection terminals of each field instrument are paralleled to each other. The physical arrangement of these transmitters, though, may vary substantially.

The simplest way to connect FF H1 devices together is the so called “daisy-chain” method, where each instrument connects to two cable lengths, forming an uninterrupted “chain” network from one end of the segment to the other:

Fieldbus Daisy-Chain Topology

Fieldbus Daisy-Chain Topology

As simple as this topology is, it suffers from a major disadvantage: it is impossible to disconnect any device in the segment without interrupting the network’s continuity.

Disconnecting (and reconnecting for that matter) any device necessarily results in all “downstream” devices losing signal, if only for a brief time. This is an unacceptable liability in most industrial applications, as it complicates maintenance and servicing of individual instruments on the segment.

An alternative topology is the bus layout, where short “spur” cables connect instruments to a longer “trunk” cable.

Terminal blocks – or even quick-disconnect couplings – within each junction box provide a convenient means of disconnecting individual devices from the segment without interrupting data communication with the other devices:

Fieldbus Bus Topology

Fieldbus Bus Topology

The ideal arrangement for a “bus” network is to minimize the length of each spur cable, so as to minimize the delay of reflected signals off the unterminated ends of the drops. Remember that only two termination resistors are allowed in any electrically continuous network segment, and so this rule forbids the addition of terminators to the end of each spur cable.

Yet another alternative topology for H1 networks is the so-called chicken-foot arrangement, where a long trunk cable terminates at a multi-point junction along with several field devices and their spur cables:

Fieldbus Tree Topology

Fieldbus Tree Topology

Most FF systems resemble a combination of “bus” and “chicken-foot” topologies, where multiple junction devices serve as connection points for two or more field instruments per junction.

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

FF Signal Status
What is HART, Foundation Fieldbus & Profibus ?
Different Types of Network Topologies
How Modbus Communication works
Difference Between Ethernet IP and EtherCAT
Foundation Fieldbus Electrical Parameters
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
1 Comment
  • Kaushikpatel says:
    March 23, 2018 at 9:58 am

    Tx bro..
    Pleash tel me bro..
    FF out put

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

7 OSI Layers of Communication
Fiber Optic Data Communication
HART Communication Interview Questions and Answers
Basics for CAN Bus Protocol – Controller Area Network
Difference Between Ethernet IP and Profinet
OPC Communication Interview Questions and Answers
WirelessHART Network Gateway Device
CANOpen Network Topology

Keep Learning

foundation-fieldbus-vs-profibus

Comparison between Foundation Fieldbus and Profibus

Difference Between Optical Fibre and Coaxial Cable

Difference Between Optical Fibre and Coaxial Cable

HART Multidrop Network

HART Communication Tutorial Part 2

Difference between Router, Switch, and Hub

Difference between Router, Switch, and Hub

Difference Between Cyclic and Acyclic Communication

Difference Between Cyclic and Acyclic Communication

FF JB Termination

Foundation Fieldbus Installation and Best Practices

Actuator Sensor Interface (ASi) Protocol in PLC

Actuator Sensor Interface (ASi) Protocol in PLC

ProfiBus Questions and Answers

Latest ProfiBus Questions and Answers

Learn More

IEC Area Classification System

Ex ic Intrinsic safety Standard

Benefits of Pursuing a Degree in Engineering

Benefits of Pursuing a Degree in Engineering

Deluge System for Transformer Protection

Deluge System for Transformer Protection Animation

Radar LT Loop Diagram

Questions on Radar LT Loop Diagram

PID Block in RSLogix 500

PID Block in RSLogix 500

What's the problem with shock and vibration

What’s the problem with shock and vibration ?

FF instrument

H1 FF Device Configuration and Commissioning

Semiconductor Fuse

What is a Semiconductor Fuse?

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?