Fire and gas detectors often use a 3-wire system rather than a 2-wire system for better functionality and safety.
Both 2-wire (also known as loop-powered) and 3-wire (typically, but not always, a separate powered device) detectors can use the 4-20 mA standard for analog signaling in industries. This standard is used because it’s relatively immune to noise and voltage drops over long distances.
In a 2-wire system, the device gets its power from the loop itself. It’s advantageous because it simplifies wiring and reduces installation costs. The devices regulate the current on the loop to represent the measured parameter (e.g., gas concentration). However, the power available to the device is limited by the loop voltage and resistance.
Therefore, if the fire and gas detector requires more power to operate correctly (for example, for heaters in certain gas detectors, or for advanced diagnostic capabilities), a 2-wire system may not be adequate.
In a 3-wire system, the device has a separate power supply, which means it’s not limited by the loop voltage and can, therefore, handle more power-intensive operations. This can be advantageous for devices that need additional power, beyond what the 4-20 mA loop can provide, to function correctly or for additional features.
So having a separate power supply can provide redundancy and improve system reliability in case of a failure in the 4-20 mA loop.
We can also go with 4-wire detectors but they will increase the project costs due to additional wire and lead to high-installation costs when compared to 2-wire and 3-wire detectors.
The 4-20 mA signals inherently mitigate issues of voltage drop over long cable runs, the distinction between 2-wire and 3-wire devices has more to do with power availability for the device operation rather than signal integrity.
The preference for a 2-wire or 3-wire system would depend on the specific needs of the detector and the power availability and requirements of the particular installation. For a device with higher power requirements or sophisticated functionality, a 3-wire system may be more appropriate, whereas a 2-wire system may be more suitable for simpler devices or for installations where wiring costs need to be minimized.
If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
Omron PLC logic for sorting the number of products and counting the number of products…
Learn the water fountain control logic using the PLC timers programming to control the high…
Open Telemetry is a framework for collecting data in cloud-native applications including tracing, metrics, and…
This article is about controlling the Pneumatic cylinder and Pneumatic motor in the assembly line…
In this post, we will learn the basic requirements for a network switch to be…
The PLC panel and MCC panel interface signals are start, stop, run feedback, trip, local…
View Comments
What do I need to follow all the courses in full and what are your conditions because I want to improve my skills in Instrumentation and control? And also is there a way to follow in French