Categories: Electrical Theory

Transformer Losses and Efficiency

All transformers have copper and core losses. Copper loss is power lost in the primary and secondary windings of a transformer due to the ohmic resistance of the windings.

Copper loss, in watts, can be found using below Equation.

Copper Loss = IP2 RP + IS2 RS

where

IP = primary current

IS = secondary current

RP = primary winding resistance

RS = secondary winding resistance

Core losses are caused by two factors: hysteresis and eddy current losses. Hysteresis loss is that energy lost by reversing the magnetic field in the core as the magnetizing AC rises and falls and reverses direction.

Eddy current loss is a result of induced currents circulating in the core.

The efficiency of a transformer can be calculated using below Equations.

Transformer Efficiency and Loses Formula

where

PF = power factor of the load

Example 1:

A 5:1 step-down transformer has a full-load secondary current of 20 amps. A short circuit test for copper loss at full load gives a wattmeter reading of 100 W. If RP = 0.3Ω, find RS and power loss in the secondary.

Solution :

Copper Loss = IP2 RP + IS2 RS   =  100 W

To find IP

I= (NS/NP) IS

I= (1/5) 20 = 4 amps

To find RS

IS2 RS   =  100 – IP2 RP

RS   =  (100 – IP2 RP ) / IS2

RS   = (100 – 4 x 0.3 ) / 202

RS   = 0.24

Power loss in secondary = IS2 RS   = 202 x 0.24 = 96 W

Example 2:

An open circuit test for core losses in a 10 kVA transformer gives a reading of 70 W. If the PF of the load is 90%, find efficiency at full load.

Solution :

You've successfully subscribed !

View Comments

    • Since Transformer doesnt produce any power rather than just only transform the Voltage and Current into high to low and low to high, for which Voltage and Ampere is related. Thats why its only rating in VA. and for larger transformer KVA and MVA is used for the rating of a transformer.

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago