Categories: Electrical Theory

Three Phase Transformer Connections

So far, our discussion has dealt with the operation of single-phase transformers. Three-phase transformer operation is identical except that three single-phase windings are used. These windings may be connected in wye, delta, or any combination of the two.

Delta Connection

In the delta connection, all three phases are connected in series to form a closed loop (Figure 1).

delta connected generator

Figure 1 : Delta Connection

Wye Connection

In the wye connection, three common ends of each phase are connected together at a common terminal (marked “N” for neutral), and the other three ends are connected to a three-phase line (Figure 2).

Figure 2 :  Wye Connection

Combinations of Delta and Wye Transformer Connections

A three-phase transformer may have three separate but identical single-phase (1φ) transformers or a single 3φ unit containing three-phase windings. The transformer windings may be connected to form a 3φ bank in any of four different ways (Figure 3).

Figure 3 :  3φ Transformer Connections

Figure 3 shows the voltages and currents in terms of applied line voltage (V) and line current (I), where the turns ratio (a) is equal to one. Voltage and current ratings of the individual transformers depend on the connections (Figure 3) and are indicated by below Table for convenience of calculations.

Example 1:

If line voltage is 440 V to a 3φ transformer bank, find the voltage across each primary winding for all four types of transformer connections.

Solution :

Δ – Δ : Primary Voltage = V = 440 Volts

Y – Y : Primary Voltage = V/√3 = 440/1.73 = 254.3 volts

Y – Δ : Primary Voltage = V/√3 = 440/1.73 = 254.3 volts

Δ – Y : Primary Voltage = V = 440 Volts

Example 2:

If line current is 10.4 A in a 3φ transformer connection, find the primary phase current.

Solution :

Δ – Δ : Primary Phase Current = I/√3 = 10.4/1.73 = 6 amps

Y – Y : Primary Phase Current = I = 10.4 amps

Y – Δ : Primary Phase Current = I = 10.4 amps

Δ – Y : Primary Phase Current = I/√3 = 10.4/1.73 = 6 amps

Example 3:

Find the secondary line current and phase current for each type of transformer connection, if primary line current is 20 amps, and the turns ratio is 4:1.

Solution :

∆-∆ : Secondary line current = 4(20) = 80 amps

∆-∆ : Secondary Phase current = aI/√3 = (4×20) / 1.73 = 46.2 amps

Y-Y : Second line current = aI = 4(20) = 80 amps

Y-Y : Second phase current = aI = 4(20) = 80 amps

Y-∆ : Second line current = √3aI = 4(20)(1.73) = 138.4 amps

Y-∆ : Second phase current = aI = 4(20) = 80 amps

∆-Y : Second line current = aI/√3 = (4×20) / 1.73 = 46.2 amps

∆-Y : Second phase current = aI/√3 = (4×20) / 1.73 = 46.2 amps

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

4 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago