This solar hot-air collector bank uses a variable-speed fan as the final control element, the temperature controller commanding the fan to blow air at different rates in order to maintain a relatively constant discharge temperature.
The hot air is being used to dehydrate wheat grain prior to grinding it into wheat flour.
Unfortunately, this system is not operating as it should – the grain is taking longer to dry out than it usually does, despite enjoying the same amount of sunlight (heat source) as it has in the past:
1. A fellow instrument technician proposes that the VFD is causing the blower motor to spin at the wrong speed, while an operator thinks the solar collectors’ glass panes probably need to be cleaned of dust and dirt accumulation. Explain why both of these hypotheses are incorrect and suggest at least two of your own hypotheses account for what we see happening in this system.
2. A valuable principle to apply in a diagnostic scenario such as this is the correspondence: identifying which field variables correspond with their respective controller faceplate displays, and which do not.
3. Determine the proper action for this loop controller (direct or reverse).
4. Why is the temperature gain less for each successive panel? Is this a problem, or do you think this is how the system normally operates?
Join the Discussion! Share your answers with us through below comments section.
In this article, we are going to discuss about shutter door control using induction motor…
Electrical Drives control the motion of electric motors. Motion control is required in industrial and…
PLC ladder logic design to control 3 motors with toggle switch and explain the program…
VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…