Multiple Choice Questions

PID Controller Multiple Choice Questions

Top PID Controller Multiple Choice Questions and answers for industrial automation engineers and control system engineers.

PID Controllers Multiple Choice Questions

Question 1

The derivative control action is typically used when controlling, but rarely used when controlling.

(A) Temperature, Flow
(B) Flow, Level
(C) pH, Temperature
(D) Level, Temperature
(E) Level, Flow

Answer : A

Question 2

processes always require some degree of control action to achieve setpoint.

(A) Integrating, Derivative
(B) Integrating, Feedforward
(C) Self-regulating, Proportional
(D) Runaway, Linear
(E) Self-regulating, Integral

Answer : E

Question 3

The reciprocal of proportional band is called:

(A) Reset
(B) Percent
(C) Minutes per repeat
(D) Gain
(E) Rate

Answer : D

Question 4

“Quarter-wave damping” may be described as:

(A) a condition of good control where PV approaches SP without overshoot
(B) a condition of poor control where oscillations continue at constant amplitude
(C) a condition of poor control where the transmitter is damped by 25%
(D) a condition of good control where oscillations quickly subside
(E) a condition of excellent control where there are no oscillations

Answer : D

Question 5

Reset control action is often expressed in units of:

(A) percent
(B) seconds per rate
(C) minutes
(D) time constant ratio (unitless)
(E) repeats per minute

Answer : E

Question 6

A proportional band setting of 175% is equivalent to a gain setting of .

(A) 175
(B) 0.756
(C) 0.571
(D) 1.32
(E) 1.75

Answer : C

Question 7

The open-loop response of a process is shown in the following trend. What sort of process is indicated by this behavior?

PID control and tuning

(A) Integrating
(B) Proportional
(C) Linear
(D) Direct-acting
(E) Self-regulating

Answer : A

Question 8

A condition where integral control action drives the output of a controller into saturation is called:

(A) self-bias
(B) wind-up
(C) repeat
(D) noise
(E) offset

Answer : B

Question 9

Fast, self-regulating processes typically respond well to aggressive control action.

(A) Nonlinear
(B) Derivative
(C) Proportional
(D) Reset
(E) Gain

Answer : D

Question 10

Process variable filtering should be used:

(A) to dampen noise
(B) only on integrating processes
(C) to improve response time
(D) only on self-regulating processes
(E) never

Answer : A

Credits : by Tony R. Kuphaldt

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago