Animation

Fire Water Sprinklers Working Principle

Automatic Sprinklers

Automatic sprinklers are thermosensitive devices designed to react at predetermined temperatures by automatically releasing a stream of water and distributing it in specified patterns and quantities over designated areas.

Principle of Operation

  1. Under normal conditions, water discharged from an automatic sprinkler is restrained by a cap or valve.
  1. The cap/valve are held tightly against the orifice by a system of levers and links, or other releasing devices, pressing down on the cap and anchored firmly by struts on the sprinkler.
  1. Attached to the frame of the sprinkler is a deflector which direct and convert the stream of water into a spray designed to cool or protect a certain area.
  1. The amount of water discharged depends upon the flowing water pressure and the size of the sprinkler orifice.
  1. The speed of operation depends on the physical properties of the thermosensitive mechanism of the sprinkler.
  1. The time involved to operate depends, amongst other factors, upon the shape, size and mass of the thermosensitive mechanism, and the temperature differential between the surrounding atmosphere and the operating temperature of the sprinkler.

The two common types of operating elements are as follows:

1.Frangible type (e.g. Quartzoid bulb sprinkler)

The small bulb, usually of pyrex glass, contains a liquid which does not completely fill the bulb, leaving a small air bubble entrapped in it. As the liquid is expanded by heat, the bubble is compressed and finally absorbed by the liquid. As soon as the bubble disappears, the pressure rises infinitely and the bulb shatters, releasing the valve cap. The exact temperature is regulated by adjusting the amount of liquid and the size of the bubble when the bulb is sealed.

2.Fusible type (e.g. Soldered strut sprinkler)

It operates upon the fusing of a metal alloy of predetermined melting point.

So, Types of Automatic Sprinklers are as follows

The 2 basic type of automatic sprinkler are:

  1. Quartzoid bulb sprinkler
  2. Soldered strut sprinkler

Quartzoid Bulb Detector

Quartzoid Bulb Detector Working Principle

The above figure shows a quartzoid bulb detector or sprinkler (QBD). In this type the sprinkler incorporates a quartzoid bulb filled with a highly expansive coloured liquid having different expansion rates. Different QBD have different temperature ratings.

When a fire occurs in an adjacent area to this bulb the fluid expands until the air space is filled, increasing internal pressure causes the bulb to fracture. The size of the air gap determines the temperature at which this failure occurs. The valve plug falls out and a jet of water exits , striking the spray generator where it is then distributed evenly over the surrounding area. In acting this way only the area of the fire is deluged and damage is minimized

Apart from the QBD we have another sprinkler we use generally called soldered type sprinkler.

Soldered Strut Sprinkler

The below shows a soldered-strut sprinkler. It consists of three bronze plates joined together by special solder. These plates hold a valve in position against an orifice in a flexible diaphragm and seal the water outlet.

When the space is hot and the fusible solder melts, the plates fall apart, the valve drops and water flows to the deflector to cause a water spray over the fire.

You've successfully subscribed !

View Comments

  • thanks for the given information. its very usefull. if u dont mind pls give the information about PLC and ladder logic programing sir.

  • it is easy to understand and helpful for tracking the error by simple way.
    thank you for good information.

Share

Recent Articles

  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

3 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

4 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

1 day ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

3 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago