Suppose this electric-driven air compressor refuses to start when the switch is in the “Auto” position, but starts up immediately when the switch is placed in the “Hand” position.
The first test performed by a technician is to measure AC voltage between test points A and F with the switch in the “Auto” position. There, the meter registers 117 volts AC. You are then called in to help:
Identify the likelihood of each specified fault for this circuit. Consider each fault one at a time (i.e. no coincidental faults), determining whether or not each fault could independently account for all measurements and symptoms in this circuit.
Identify the below mention faults are possible or impossible?
Also, comment on whether or not the initial test between points A and F was a useful one (i.e. did it provide any new information to help diagnose the problem?).
Answer:
The initial test between points A and F was useless. We already knew from the symptom of the compressor running in “Hand” but not in “Auto” that the fault must be an open, and it must lie between the Hand/Off/Auto switch and test point A somewhere.
An open fault anywhere between points A and F would of course drop the full control voltage, so the measurement of 117 volts AC should come as no surprise.
Share your answers with us through the below comments section.
Read Next:
Credits: Tony R. Kuphaldt
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…
This article explains how to blink lights in ladder logic with a detailed explanation video…
In this article, a simple example will teach you the conversion from Boolean algebra to…
In this article, you will learn the PLC cooking timer example for kitchen automation using…
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…