Difference between Absolute, Gauge and Differential Pressure Transmitters
To select the right pressure sensor for a specific application besides the pressure range first of all the type of pressure measurement has to be considered. Pressure sensors measure a certain pressure in comparison to a reference pressure and can be divided into absolute, gauge and differential devices.
These terms will be explained on the basis of the piezoresistive pressure sensors.
Fig : Comparison of absolute, gauge and differential pressure
Absolute pressure is referred to the vacuum of free space (zero pressure).
In practice absolute piezoresistive pressure sensors measure the pressure relative to a high vacuum reference sealed behind its sensing diaphragm.
The vacuum has to be negligible compared to the pressure to be measured.
Fig : Principle of an absolute pressure sensor (piezoresistive technology)
Examples
Gauge pressure is measured relative to the ambient atmospheric pressure. The average atmospheric pressure at sea level is 1013.25 mbar.
Changes of the atmospheric pressure due to weather conditions or altitude directly influence the output of a gauge pressure sensor.
A gage pressure higher than ambient pressure is referred to as positive pressure. If the measured pressure is below atmospheric pressure it is called negative or vacuum gauge pressure. In general a vacuum is a volume of space that is essentially empty of matter.
According to its quality vacuum is divided into different ranges such as e.g. low, high and ultra high vacuum.
Gauge pressure sensors only offer one pressure port. The ambient air pressure is directed through a vent hole or a vent tube to the back side of the sensing element and thus compensated.
Fig : Principle of a gage pressure sensor (piezoresistive technology)
Examples
Differential pressure is the difference between any two process pressures p1 and p2.
Therefore, differential pressure sensors must offer two separate pressure ports with tube or threaded connections.
Generally these pressure sensors are able to measure positive and negative pressure differences, i.e. p1>p2 and p1<p2. These sensors are called bidirectional differential pressure sensors with ranges of e.g. -1…+1 bar or -2.5…+2.5 mbar.
In contrast, unidirectional differential pressure sensors only operate in the positive range (p1>p2) e.g. from 0…1 bar or 0…2.5 mbar and the higher pressure has to be applied to the pressure port defined as “high pressure”.
Fig : Principle of a differential pressure sensor (piezoresistive technology)
Examples
Source : first-sensor
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…
This article explains how to blink lights in ladder logic with a detailed explanation video…
In this article, a simple example will teach you the conversion from Boolean algebra to…
View Comments
is this possible we can use absolute pt as a gauge pt by absolute zero trimming ?