Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Pneumatic Force Balance Instrument
Share
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Practical Questions > Pneumatic Force Balance Instrument

Pneumatic Force Balance Instrument

The sensitivity and linearity of pneumatic force-balance instruments improved with a pneumatic amplifying relay.

Last updated: September 25, 2020 12:48 pm
Editorial Staff
Practical Questions
No Comments
Share
7 Min Read
SHARE

The sensitivity and linearity of a pneumatic force-balance instruments may be improved with the addition of a pneumatic amplifying relay to amplify the response of the flapper/nozzle assembly.

Contents
Pneumatic InstrumentWorking

In other words, the inclusion of an amplifier into the system increases the system’s gain. Explain what happens, step by step, in the system shown, if force is applied to the lever by someone’s thumb:

Pneumatic Instrument

Pneumatic Force Balance Instrument

Also, determine whether the mechanism will still produce the same amount of output pressure for any given amount of applied force without the amplifying relay in place.

In other words, if we removed the relay from the system, would the output pressure be greater than before, less than before, or the same as before given the same force applied to the lever?

Pressure based Relay

Challenge question: if we reduced the restriction (orifice) bore size in this system such that less air flowed through the nozzle, would the output pressure be greater than before, less than before, or the same as before given the same force applied to the lever?

Working

The particular pneumatic amplifying relay shown is the one typically used in Foxboro pneumatic instruments. It is not the only type of amplifying relay design, but a very common one.

Foxboro pneumatic instruments

If the lever is pushed toward the nozzle by an external force, the following will happen:

  • Pressure upstream of the nozzle will increase, as the nozzle becomes more restricted by the flapper.
  • This pressure, going to the relay through the “input” port, will push up on the relay diaphragm.
  • The relay diaphragm lifts up, pushing the stem valve closer to its seat, and lifting the ball off of its seat.
  • As the ball lifts off its seat, more supply air is allowed to go into the area between the ball and stem.
  • As the stem closes on its seat, the passage from this middle area to the vent port becomes more restrictive.
  • As a result of the previous two factors, the output air pressure to the bellows will increase dramatically.
  • The bellows will expand, pushing to the right on the lever.
  • As the flapper will move to the right until a condition of equilibrium is reached with the force from the thumb.

The operation of the pneumatic relay might require a bit more explanation for full understanding. The “input” pressure sent to the relay from the nozzle tube pushes against the full area of the diaphragm, creating an upward force.

Since the area above the diaphragm is vented (at atmospheric pressure), there can be no substantial pressure buildup on the top side of the diaphragm, and thus no downward force generated by the diaphragm to counter the input pressure’s an upward force:

operation of the pneumatic relay

This force acts to lift the “ball” valve off its seat and also close the cone-shaped “stem valve,” adding more pressure to the output chamber by opening the passage for supply air to enter and closing the passage for air to vent, respectively:

Pneumatic relays

The only force opposing the diaphragm’s upward motion is a small leaf spring pressing down against the ball. This spring is not very strong, meaning that small changes in input pressure result in large changes in output pressure. In other words, the pneumatic amplifying relay has a very large gain.

Pneumatic relays such as this serve the same purpose as operational amplifiers in electronic circuits: amplifiers with extremely high gains, used within negative feedback loops to achieve some lesser amount of amplification that is very nearly linear.

In this particular example, the final result (flapper, nozzle, lever, relay, and bellows) is a force-balance system that aggressively responds to any external force applied to the lever, such as the force exerted by someone’s thumb.

In a real pneumatic instrument, this external force would represent some signal or process variable, and the balancing pressure at the bellows would be the instrument’s pneumatic output signal.

The presence or absence of the pneumatic amplifying relay does not alter the pressure/force relationship of this mechanism. The relay merely increases sensitivity to small changes in force and increases the speed of response.

Answer to challenge question: although narrowing the restriction would decrease nozzle air flow, this would have no effect on the pressure/force relationship of this mechanism. It is still a force-balance system where bellows force must equal applied force to reach a state of equilibrium, and this bellows force is strictly a function of nozzle pressure (F = PA) not nozzle flow rate.

It should be noted that the actual gain of the pneumatic amplifier  (∆Pout/∆Pin) is irrelevant, so long as it is arbitrarily large. This is analogous to the open-loop voltage gain of an operational amplifier being largely irrelevant to the overall voltage gain of a negative-feedback circuit.

In other words, the presence of this amplifying relay does not alter the input force/output pressure relationship of this pneumatic mechanism.

In order to alter the pressure/force relationship of this mechanism, one would have to alter the feedback components: either change the effective area of the bellows or the moment arm through which it acts to counteract the applied force.

Interest to add any further points? Share your answers with us through the below comments section.

Read Next:

  • What is Nest Loading?
  • Interposing Relay Panel
  • Control Valve Testing
  • Pneumatic Control Loop
  • Pneumatic Instrumentation

Credits: Tony R. Kuphaldt

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Guided-wave Radar Asset Management Parameters
Question on Analytical Controller
Current-to-Pressure Transducer Calibration Table
Calculate the appropriate millivoltage values of a Thermocouple
Practical Process Control System Questions & Answers – 3
Programmable Logic Controller (PLC) Questions and Answers – 6
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

10 Questions on Reforming Furnace Control System
Define Normal Status for each of the Process Switch
Investigate High Level Alarm of Distillation Process
Pneumatic Relay Questions
Problem on Tachogenerator
Which Instrument is at Fault in this System?
Calculate Amount of Weight Indicated by the Scale
Analytical Control System of Heat Exchanger Questions

Keep Learning

solenoid valves trip

Identify Solenoid Valves Energized or de-energized?

Inductive proximity switches

How to Connect Proximity Switch (Source Type) to Make LED ON ?

Programmable Logic Controller (PLC) Questions and Answers

Programmable Logic Controller (PLC) Questions and Answers – 1

Explain What these Spool Valve Represent

Explain What these Spool Valve Symbols Represent?

Problem with Pirani Gauge

Problem with Pirani Gauge

Radar LT Loop Diagram

Questions on Radar LT Loop Diagram

Double Block and Bleed Valves Opening or Closing Sequence

Double Block and Bleed Valves Opening or Closing Sequence

Draw the Symbols for Liquid Level Measuring Instruments

Draw the Symbols for Liquid Level Measuring Instruments

Learn More

Free Omron PLC Programming Course in HINDI

Free Omron PLC Programming Course in HINDI

Butterfly Valve

Butterfly Valves Construction, Types, Stem & Bonnet Assembly

Loop Diagram

Documentation and Change Control of PLC or DCS Systems

Pressure Transmitters Installation Factors

Pressure Transmitters Installation Tips

Optical Torsion Meter Principle

Optical Torsion Meter Principle

Various Types of Sensors Used in Water Treatment Plant

Various Types of Sensors used in Water Treatment Plant

PLC Sequential Operation Example Program

PLC Sequential Operation Example Program

PLC program pushbutton switches

PLC Permissive for Motor Control

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?