Voltage Variations Effects on Power Plant Equipment

When the voltage at the terminal of the electrical equipment deviates from the value as specified from the name plate the equipment performance and life time of the equipment are effected. IEEE Standard 666 details regarding this. The effect on the equipment may be of minor or major serious depends on the voltage deviation magnitude and the sensitivity of the equipment for the voltage variations.

Some of the equipment deviations which has certain effect due to supply voltage deviations are seen here:

Induction Motors:

Induction Motor voltage below name plate rating will result in decrease in the starting torque of the motor and increase in the full load temperature rise.

On the other hand, increase in the supply voltage above the specified voltage will results in increase in the starting torque of the motor, increase in the inrush currents during starting and decrease in the power factor.

Increase in the starting torque to above supply voltage results in acceleration of the coupling or driven equipment. Increase in the starting currents results in voltage drop in the bus connected to the motor. This effects the performance of the other loads connected to the bus.

Supply voltage above the rating will have less impact on the induction motor compared to under voltage condition but if voltage above 110% of the rated voltage will saturate the stator iron (flux is proportional to voltage / frequency) thereby damaging the magnetic properties and increase in losses.

Synchronous Motors:

Synchronous motors will have same impact as induction motor except the speed of synchronous motor remains same. Maximum or pull out torque varies directly with the voltage if the field remains constant.

Transformers:

Under-voltage operation does not have significant impact on transformer, but due to under-voltage condition current drawn by the loads increases. If this increase in load current can create an over current condition. Transformer can be operated upto 110% at no load and 105% at full load without any harm. Further increase in voltage can results in the saturation of magnetic core thereby increasing the magnetizing current and losses. Continued operation in over excited region can result in failure of unit.

 Lighting:

Fluorescent lamps operate satisfactorily over a range of + or – 10% of the ballast name plate rating compared to Incandescent lamps. Life of Fluorescent lamps are less affected compared to Incandescent lamps

You've successfully subscribed !
Share

Recent Articles

Immersion Heaters in Lube Oil Consoles
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

3 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago