Silicon Carbide Lightning Arresters Working Principle

Silicon Carbide Arresters (SIC):

The Non linear lightning arrester basically consists of set of spark gaps in series with the silicon carbide non linear resistor elements. Lightning arresters are connected between the phase conductors and ground. During normal system operating voltage conditions, the spark gaps are non conducting and isolate the high tension (HT) conductors from the ground. However whenever an overvoltge of magnitude dangerous to the insulationSilicon Carbide (SIC) Arresters Working of the apparatus protected occurs ( these over voltages or over surges may be caused due to lightning strikes on the conductors or due to Extra High Voltage (EHV) switching) the spark gap breaks down and allows the high voltage surge current to flow through the ground.

Working Principle of Silicon Carbide (SIC) Lightning Arresters:

The volt-ampere characteristics of the non linear resistor in the lignting arrester can be approximately described by expression V = KIβ. Where K and β are dependent on the composition and manufacturing process of the Non linear Resistor (NLR). The value of β lies generally in the range of 0.3 and 0.45 for modern silicon carbide (SIC) lightning arresters. If the voltage across the Non Linear Resistor (NLR) doubles, the current would increase approximately by 10 times

Therefore, with multiple spark gaps arresters can withstand high Rate of Recovery Voltage (RRRV). The non-uniform voltage distribution between the gaps (which are in series in lightning arresters) presents a problem. To overcome this, capacitors and non-linear resistors are connected in parallel across each gap. In case of lightning arresters employed for high voltage applications, capacitors and nonlinear resistors are connected across the stock of gaps and NLRs. With the steep voltage wave surge the voltage is mainly controlled by the capacitor and at the power frequency by the non-linear resistors. It is obvious that when the over voltages cause the break down of the series gaps, the current would be very high so as to make the voltage to subside very fast. The highest voltage that appear across the lightning arrester would be either the spark over voltage of the arrester or thevoltage developed across the non-linear resistor during the flow of surge current. The lowest spark over voltage of the arrester is called the hundred percent impulse spark over voltage of the arrester. The voltage developed across the non-linear resistor during the flow of surge current is called residual voltage. The lower the value of the voltage developed the better the protection of the lightning arrester

Disadvantages of Silicon Carbide (SIC) Arresters:

Some of the disadvantages of silicon carbide arresters compared to gapless arresters are given below:

  • Silicon Carbide (SIC) arresters have inferior V-I Characteristics compared to Zno arresters (Metal oxide arresters).
  • Decrease in energy absorption (surge wave) capability compared to Zno arresters.
  • Probability of sparking between the gaps.

Advantages of Silicon Carbide (SIC) Arrester :

  • Due to the presence of gaps the normal power frequency voltage during normal operation is negligibly less compared to gap less arresters. Hence no leakage current flow between the line and earth in SIC arresters
You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago