Categories: Fire & Gas System

Fire and Gas System Loop Checks Procedure

Guidelines to be followed by Panel Engineer during Fire and Gas System Loop Checks:

1. Location of the FGS Tag no. to be checked (As per Drawing, it should be on that particular area or near the particular equipment)

2. Tag number & Description of the Tag to be checked.

3. Range of that Particular instrument to be checked. (As per Instrument index)

4 5. Color of the Display (Normal: Green, Abnormal: Red blinking; Acknowledged Alarm: Static Red; Fault value: Yellow)

6. For Detectors – The checks will be done for 0%,20%,50% & 100% of the total range. 20% value will appear in Amber Color. 50% value will appear in Red color.

7. For Detectors & MCP : Normal, Abnormal & DCS Alarm values, if any, & Fault alarm to be incorporated & to be checked by simulating from field & alarm to be checked in Alarm summary.

8. For Detectors, Hooters, Beacon : Normal, Abnormal & Fault alarm to be simulated & checked. And also confirm with Field Engineer that Sound was more Audible & Beacon bulb glowing was bright. Gas Beacon & Gas Hooter will appear in Amber Color when there is a alarm in Graphics. Fire Beacon & Fire Hooter will appear in Red Color.

9. For Building Alarms from FAP (Fire Alarm Panel): Normal, Abnormal & Fault alarm simulation to be checked.

10. If there is any deviation from the above, please write your observations in Loop Test Report & DPR (Daily Progress Report).

11. Mark in F&G layout P&ID after loop check.

Also Read: How to do logic Checks

Guidelines to be followed by Field Engineer during Fire and Gas System Field Loop Checks:

1. Location of the F & G Device instruments (As per Drawing, it should be on that particular area or equipment)

2. Position of that F & G Device in field to be verified. (For eg: MCP are to be placed more than 5 metres away from Hydrocarbon area)

3. Name plate of that instruments (Should match with Drawing)

4. For Detectors, the checks will be done for 0%, 20%, 50% & 100% of the total range. The readings displayed to be counterchecked with the person on DCS.

5. For Beacon & Hooters, it will be simulated from Control Room, Visual lamp flashing to be checked in field (Gas Beacon – Yellow color & Fire Beacon – Red color).

6. For Hooters, it will be simulated from Control Room, Audible Sound to be checked in field. Eg. If they are simulating Gas Hooter from Control, only Gas Hooter in Field should sound. Both Hooter – Gas & Fire Hooter, sounds should be different.

7. If there is any deviation from the above, please note & inform your observations to the Person in Control Room, so that he will write in Loop Test Report & DPR (Daily Progress Report).

Note: Colors, graphics, Philosophies, etc… may change from industry to industry.

Also share any points if we missed in the above list via comments section.

Also Read: How to do DCS/Field Loop Checks

You've successfully subscribed !

View Comments

Share

Recent Articles

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

7 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

7 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago