Closed tank DP Level Transmitter with cleaning leg Calibration

Schematic Diagram of a Closed tank DP Level Transmitter with cleaning leg Calibration
Closed tank DP Level Transmitter with cleaning leg Calibration
Closed tank DP Level Transmitter with cleaning leg Calibration

Formulas:

Min range = SG x h

Max range = SG x h

Example:

If the height of an X is 5 meters in which there is a liquid that has a density of 1 g / cm3, what is the range of calibration on the transmitter?

SG = 1

Min range = SG x h
= 1 x 0 m
= 0 mH 2 O

Max range = SG x h
= 1 x 5 m
= 5 mH 2 O

The transmitter Range = 0 to 5 mH 2 O

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

7 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago