Differential Pressure (DP) Level transmitter Installed Above Tapping Point

Open Tank Level Measurement (Single Seal Application) Transmitter installed above Tapping Point
Differential Pressure (DP) Level transmitter Installed Above Tapping Point
This calculation used for open tank level measurement with transmitter installed above tapping point

The formulas for calculating transmitter URV and LRV are as follows:

HP Side or LRV or Transmitter 0% = Hmin.S1 – X.S2

LP Side or URV or Transmitter 100% = Hmax.S1 – X.S2

Where

S1 = Specific gravity of tank liquid.
S2 = Specific gravity of seal liquid.
Hmin = Equivalent head of water at minimum level.
Hmax = Equivalent head of water at maximum level.
X = Distance between transmitter and tapping point.

NOTE:

1. The Parameters H,X can be entered in any units like mmh20, inh20 but must be same

2. If you are using direct tubing from tapping point to transmitter without filling any additional liquid (Like water) that means you are not using any special seal liquid, so S2=S1, Here Specific gravity of Process liquid only considers for both S1 & S2. Hence S1=S2.

The Following tables specifies the seal liquid constant values:

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

7 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

1 week ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago