Multiple Choice Questions

Actuators Questions and Answers

Actuators Questions and Answers

1. A valve positioner :

a. Takes the place of a cascade control system
b. Provides more precise valve position
c. Makes a pneumatic controller in necessary
d. Provides a remote indication of valve position

Answer: b

2. Assume that a control valve regulates stream flow to a process and that high temperature makes the reaction hazardous. The usual pneumatically operated control valve utilizes the following action for fail-safe operation

a. Air to open
b. Air to close
c. 3 psi (20 kpa) to fully open
d. 15 psi (100 kpa) to fully close

Answer: a

3. The basic function of the spring in a control valve is to

a. Characterize flow
b. Oppose the diaphragm so as to position the valve according to signal pressure
c. Close the valve if air failure occurs
d. Open the valve if air failure occurs

Answer: b

4. A diaphragm actuator has a diaphragm area of 50 square inches and is adjusted to stroke a valve when a 3 to 15 psi (20 to 100 k Pa) Signal is applied. If the signal is 15 psi (100 k pa) the force on the valve stem will be :

a. 750 pounds
b. 750 pounds less than the opposing spring force
c. Dependent on hysteresis
d. None of the above

Answer:b

5. A high- pressure flow process requires a valve with tight packing. This would suggest that :

a. A valve positioner should be employed
b. The actuator must be sized to provide adequate force
c. Oversized pneumatic signals lines are required
d. The controller supplying the signal to the valve must have a very narrow proportional band.

Answer: b

6. An electronic controller creates a 4 to 20mA dc signal that must actuate a steam valve for temperature control. The best and most economical choice would be to :

a. Use an all-electric actuator system
b. Convert to a pneumatic signal at the controller and use a pneumatic actuator.
c. Use pneumatic actuator with an electric to pneumatic valve positioner
d. None of the above

Answer:c

7. A pressure control process using proportional plus integral control has a time constant of 10 seconds. The best choice of actuator would be :

a. An electric motor
b. A pneumatic diaphragm
c. A piston and cylinder
d. A solenoid electrical

Answer: b

8. A diaphragm actuator has a diaphragm area of 115 square inches. A valve positioner is attached to the actuator and fed with 22 psi air supply. If after 9 psi signal is received from the controller the signal changes to 10 psi and the valve fails to move. What is the force applied to the valve stem?

a. 2.530 pounds
b. 1.495 pounds
c. 1.035 pounds
d. None of the above

Answer: a

9. One advantage of an electric to pneumatic valve positioner is :

a. It can be used on flow control
b. It produces positive valve position
c. It conserves energy
d. It dampers valve travels

Answer: b

10. A single seated globe valve containing a plug 1 1/2 inches in diameter is used in a line pressurized to 500 psi. What actuator force is required for tight Shutoff.?

a. 884 pounds
b. 2,000 pounds
c. Depends upon direction of flow through the valved
d None of the above

Answer: c

You've successfully subscribed !

View Comments

Share

Recent Articles

How to Blink Lights in Ladder Logic?
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago