Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: What is NAMUR NE 43?
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Standards > What is NAMUR NE 43?

What is NAMUR NE 43?

Last updated: July 11, 2020 12:45 pm
Editorial Staff
Standards
2 Comments
Share
3 Min Read
SHARE

Well NAMUR NE 43 is in trend to be mentioned with 4-20 mA output.

Contents
NAMUR NE 43How this happens !1. Transmitter Failure Identification :-2. Process Variable has gone under-Range or Over Range :-Under-Range :-Over-Range:-NOW Physical Problems :-3. Short Circuited wire :-4. Open Wire :-Author : Asad ShaikhArticles You May Like :

It is said it increases diagnostic features ?

But what can you do more in 4-20 mA ?

NAMUR NE 43

Well as per API 551 recommendation following things can be distinguished when signal levels are properly defined :-

  1. When the process variable has increased beyond transmitter calibrated range and transmitter has gone into saturation
  2. When the transmitter is faulty and it is not the process variable range that is driving transmitter to saturation
  3. When the transmitter wire is short circuited
  4. When the Transmitter wire is open

How this happens !

1. Transmitter Failure Identification :-

On failure of transmitter , The Transmitter is configured to output LOW or HIGH

This LOW Range can be between 3.6 to 3.8 mA

This HIGH Range can be between 20.5 to 22 mA

NOTE:-This between means we select a value as per our requirement .

E:G :- Factory setting for E+H Transmitter is 22mA

2. Process Variable has gone under-Range or Over Range :-

Under-Range :-

Between 3.8 to 4 mA would state that process variable has gone below the calibrated range but THE TRANSMITTER IS NOT FAULTY

Over-Range:-

Between 20 to 20.5 mA would state that process variable has gone above the calibrated range but THE TRANSMITTER IS NOT FAULTY

The below table from API 551 makes it clear

NAMUR NE 43

NOW Physical Problems :-

Suppose the Transmitter is working fine

Also the process variable is between the calibrated range .

BUT some physical limitation occurs .

3. Short Circuited wire :-

Suppose the Transmitter is working fine

Also the process variable is between the calibrated range .

BUT the wire is short circuited so a high amount of Current will flow through the circuit .

This high amount of current is defined as Greater than 22 mA (As mentioned in API 551 you could change as per your preference)

Note :- this definition differs from project to project after what predetermined value do you want it to detect a short circuit.

4. Open Wire :-

What if the wire comes out , gets cut etc..

This is also on of the driving factors we have 4 mA as starting and not 0 mA .Live Zero Concept .

Open field is defined as 0 to 3.6 . ( this is if wire is partially cut or completely cut )

Thanks for reading !!

PS : As always, This is as per best of my understanding !

Author : Asad Shaikh

Profile : Linkedin

Articles You May Like :

Basics of Loop Checks

3-15 psi to 4-20 mA Conversion

4–20 mA Process Control Loop

HART Communication Protocol

Live Zero in 4-20 mA Current Loop

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Gas Detectors Standards
Pre-Startup Safety Review (PSSR)
Hazardous Area Classification markings
Purge & Pressurization Systems Interview Questions
Standard Temperature and Pressure Conditions
IP Ratings and Equivalent NEMA Ratings
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
2 Comments
  • Dave says:
    December 22, 2019 at 5:34 am

    I think 3.8 to 3.6 and 20.5 to 22 are not the correct ranges. NAMUR compliant failed state should be represented by an output below 3.6 or above 21.0. There is different / conflicting info on this topic, and I am going to get a copy of the NE43 to verify this, but I think you should check your values.

    Reply
    • Zhou Weiyong says:
      August 14, 2024 at 8:06 am

      Agree with you, but different vendor has different setting value for hardware fault ,anyway the value should be below 3.6 or above 21.0.

      Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

RTD Standards
Why is IEC 60269 Important? – Electrical Applications
Purging of Instruments
NAMUR NE107 Standard
Explosive Atmospheres & Hazardous Classification
ATEX Ratings, Intrinsic Safety, Hazardous Areas and Explosive Atmospheres
What is IEC 61508 ?
Pressure Standards
Hazardous Areas in Industry – Electrical Equipment Selection
ISA codes for Process Instrumentation

Keep Learning

Valve Standards

List of Valve Standards

Hazardous Area Terminology

Hazardous Area Terminology

Hazardous Area Questions & Answers

Hazardous Area Classification Questions

Instrumentation Standards

Electronic Equipment Purging Principles & Standards

Intrinsic Safety Zones

Intrinsic Safety Protection ia and ib

Transmitters 4-20mA Current Failure Alarm Limits

Transmitters 4-20mA Current Failure Alarm Limits

HAZOP

What is HAZOP ?

NEMA to IP Ratings

NEMA Enclosure Types Standards

Discover More

Electrical Machines Questions and Answers

Equivalent Circuit of Transformer

In this article, you will learn the configuration of PlantPAx library in factory talk studio of Rockwell Automation.

Configuration of PlantPAx Library in Factory Talk Studio

Ethernet Switch Animation

Ethernet Bus Animation

Electropneumatic Valve Positioner Working Principle

Electro Pneumatic Valve Positioner Schematic & Principle

Magnehelic Gauge Calibration

Magnehelic Gauge Calibration

Why Baud Rate is Important in Modbus Network

Why Baud Rate is Important in Modbus Network?

Tips for Reducing the Noise Signals

Tips for Reducing the Noise Signals

Instrumentation Cables Testing Standards

Instrumentation Cables Testing Standards