Why rating of Synchronous Generators and Alternators in MVA or KVA

Normally the rating of synchronous generators or alternators will be in KVA or MVA instead of kW rating.

Electrical apparatus or machines are usually rated the load which it can carry without overheating and damaging to insulation. i.e, rating of the electrical machines are governed by the temperature rise caused by the internal loss of the machine. The copper loss in the armature depends on the strength of the armature current and core loss depends on voltage and these losses are independent of the power factor.

The reason for which the transformers and synchronous generators are rated in volt-amperes instead of watts is that manufacturer does not know at what power factor does these equipments are going to operate. On the other hand while manufacturing the motors manufacturer specifies the power factor at which the motor should be operate. This is the reason why the motor loads (including synchronous motors are rated in kw) are rated in wattage power.

In the case of alternator and transformers manufacturer does not know the operating power factor. Hence they are rated in KVA or MVA

Consider a generator whose output power is 1000kVA, for different power factors 0.2, 0.5 and 0.8 and unity respectively the output power in kW will be 200, 500, 800 and 1000kW.

You've successfully subscribed !
Share

Recent Articles

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago