WirelessHART Transmitter With Gateway
This guide is intended to give an idea on how to use 375/475 Field Communicator to configure Rosemount wireless device to be connected to wireless gateway
Follow below steps :
STEP 1 : Plug the Connector set into HART terminal at 375/475
STEP 2 : Clip the other end of Connector to the COMM terminal.
STEP 3 : Insert the Battery module into the dedicated slot
STEP 4 : Power Up the 375/475. Select the “HART” icon and press “Enter” keypad to communicate with the Transmitter
STEP 5 : Please wait until 475 fully load the device DD. Then go to “Configure”
STEP 6 : Go to “Manual Setup”
STEP 7 : Go To “Wireless”
STEP 8 : Go to “Join Device To Network”
STEP 9 : Key in the Network ID. Then press “Enter”. The ID should be the same as configured in Wireless Gateway.
STEP 10 : Key in the 4 parts of the Join Key. Press “Enter” to proceed. The Join Key should be the same as configured in Wireless Gateway.
STEP 11 : Press “Enter” to Accept new join key. The device will attempt to connect with the Wireless Gateway. This may take few minutes.
Note: Depend on the device, the steps may vary. Set to the device lowest burst rate and enable gateway for “Active advertising” to speed up the connection process. The guide is for Rosemount devices
Configuration of Remaining process parameters will be as same as wired HART Transmitters.
In this post, a new wireless device is added to the control system and the measurement it provides is added to a control module. It is assumed that the wireless gateway has been added to the control system LAN and assigned to the controller.
Step 1: Configure a new wireless device using a field communicator. Enable the burst mode to publish data. Power it on and let it join the wireless network.
Step 2: In the control system explorer view of field devices, open the Reconcile I/O dialog box, find the new device and, drag and drop it to an unused channel.
Step 3: Create a new control module and, assign it to the controller. Add an AI function block and assign its IO_IN to the tag of the channel assigned to the new device.
Step 4: Download the controller.
Step 5: Open the control module online and observe that the value of the AI block periodically updates. The updates come from the burst data of the new device.
Credits : MKR MN
VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…