Advantages of Bundled Conductors in Transmission Lines

For transmission of more power for long distances to load centers Extra High Voltage (EHV) transmission is employed. Implementing Extra High Voltage has advantage of reduction in the copper losses and improves efficiency.

However transmission of voltage beyond 300kV will poses some problems such as Corona effect which causes significant power loss and interference with communication circuits if round single conductor per phase is used. In order to reduce corona effect hollow round conductors are used. Keeping economical constraints other option is instead of using hallow round conductor it is preferable to use more than one conductor per phase which is called Bundled Conductors. For transmission of power beyond 400kV bundled conductors are employed.

Advantages of Bundled Conductors in Transmission Lines
Bundled Conductors in Transmission Lines

Advantages of Bundled Conductors:

Bundled conductors are primarily employed to reduce the corona loss and radio interference. However they have several advantages:

  • Bundled conductors per phase reduces the voltage gradient in the vicinity of the line. Thus reduces the possibility of the corona discharge. (Corona effect will be observed when the air medium present between the phases charged up and start to ionize and acts as a conducting medium. This is avoided by employing bundled conductors)
  • Improvement in the transmission efficiency as loss due to corona effect is countered.
  • Bundled conductor lines will have higher capacitance to neutral in comparison with single lines. Thus they will have higher charging currents which helps in improving the power factor.
  • Bundled conductor lines will have higher capacitance and lower inductance than ordinary lines they will have higher Surge Impedance Loading  (Z=(L/C)1/2). Higher Surge Impedance Loading (SIL) will have higher maximum power transfer ability.
  • With increase in self GMD or GMR inductance per phase will be reduced compared to single conductor line. This results in lesser reactance per phase compared to ordinary single line. Hence lesser loss due to reactance drop.
You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago