Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Manual Call Point Testing Procedure
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Fire & Gas System > Manual Call Point Testing Procedure

Manual Call Point Testing Procedure

Here in this article, we discuss the general testing or healthiness checking procedure of an Manual Call Point (MCP) of fire alarm panel.

Last updated: August 21, 2020 10:08 am
Editorial Staff
Fire & Gas System
No Comments
Share
3 Min Read
SHARE

Here in this article, we discussed the general testing or healthiness checking procedure of a Manual Call Point (MCP) of fire alarm panel.

Contents
Manual Call Point Testing ProcedureRead Next:

Manual Call Point Testing Procedure

Manual Call Point Testing Procedure

Before starting the job, take the proper work permit and inform to all the respective departments. Also, do force the respective logics or interlocks if any (like fire suppression systems activation etc)

  • Remove all the screws and remove the glass cap from MCP.
  • After removing the glass cap from MCP,  the switch inside it activates so alarm appears on Fire alarm panel and the hooter is activated.
  • Acknowledge the alarm or silence the hooter on the fire alarm panel.
  • Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the MCP tag number and installed location.
  • Confirm the MCP activation status from the respective graphics page. You have to visually identify the color change signals of the respective MCP on the graphics.
  • Check the + 36 Volts DC Supply on Monitor Module between terminal 1 and 2. (This is the circuit module inside the MCP).
  • Check all the wire connections on Monitor Module, the push button contact if it found loose then tighten them fully.
  • Ensure resistor leads are completely tightened on to the terminals of the circuit in MCP.
  • Clean the MCP dust by brush and cotton cloth.
  • Fix the glass cap of MCP and fix all screws. It should be fully tightened. If it is loose alarm reappears.
  • Reset the alarm signal from the Fire Alarm Panel.
  • Now MCP is working now in Normal condition.
  • Repeat the above procedure for all the remaining MCP’s.
  • Normalize the forced interlocks or logics if any.
  • Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Manual Call Point.

Author: V Hemanth

Read Next:

  • Fire Detectors Questions
  • Linear Heat Detectors
  • Thermal Detectors Principle
  • Fire Alarm Control Panel
  • Types of Fire Detectors
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Recommended Articles

Basics of Sprinkler System
Rate Compensated Heat Detectors Working Principle
Gas Detectors Working Principle
Why we use End of Line (EOL) Resistor in Fire and Gas System ?
Basics of Fire Detection and Alarm System
What is an Explosive Limit? – Lower Explosive Limit (LEL)
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • William Snyder on Top Non-PLC Certification Courses for Automation Professionals
  • Kamli on Top Free PLC Software
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals

Related Articles

Beam-Detectors-Working-Principle-2

Beam Detectors Working Principle Animation

Flame Detector Testing Procedure

Flame Detector Testing Procedure

Fire and Gas System

Types of Fire and Gas Detectors

Why Fire and Gas Detectors are 3-Wire types instead of 2 Wire

Why Fire and Gas Detectors are 3-Wire types instead of 2 Wire?

Argonite/CO2 Flooding System Master & Slave Cylinder Operation

How to use Fire Fighting Hydrant

Fire and Safety

oxygen Safety Analyzer

Oxygen Safety Analyzer

Gas Detector Types

Sensor Technologies in Gas Detectors

More Articles

Target Flow Transmitter Problem

Target Flow Transmitters Failed the Very Midnight

What is Oscilloscope

What is Cathode Ray oscilloscope ?

What is an HRC Fuse

What is an HRC Fuse? – Material, Types, Advantages

Power Electronics Interview Questions & Answers

Power Electronics Interview Questions & Answers

Causes of PLC Stop Mode

Various Causes for PLC Going in Stop Mode

fieldbus cables layout

H1 FF Data Link layer

How to Upload PLC Program in Siemens PLC if Upload Icon is Disabled