Reading: Something is Wrong with Strain Gauge Bridge Circuit
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Practical Questions > Something is Wrong with Strain Gauge Bridge Circuit

Something is Wrong with Strain Gauge Bridge Circuit

Last updated: June 4, 2020 9:18 am
Editorial Staff
Practical Questions
No Comments
Share
3 Min Read
SHARE

A strain gauge is an array constructed from thin metal film designed to increase resistance as it is stretched and decrease resistance as it is compressed.

Strain gauges are typically bonded to metal specimens undergoing mechanical testing, as a means of sensing how much strain is being applied to that metal specimen.

In order to translate the resistance of the strain gauge into a measurable voltage signal, the strain gauge is typically incorporated into one arm of a “bridge” circuit.

Strain Gauge Bridge Circuit

The following bridge circuit uses two strain gauges (one to measure strain, the other to compensate for temperature changes), the amount of strain indicated by the voltmeter in the center of the bridge. Unfortunately, though, it has a problem.

Instead of registering a very small voltage as it normally does, the voltmeter is “pegged” (driven beyond its normal full-range measurement) by a large voltage difference, with point B positive and point A negative as shown here:

Strain Gauge Bridge Circuit

Something is wrong in the bridge circuit, because this voltage is present even when there is no physical stress on the specimen. Identify which of the following faults could cause the excessive voltage to appear across the voltmeter, and which could not. Consider only one of these faults at a time (no multiple or simultaneous faults):

The below list shows the different types of faults. Identify which faults are possible to occur and which are not.

  • R1 failed open
  • R2 failed open
  • Strain gauge failed open
  • Dummy gauge failed open
  • R1 failed shorted
  • R2 failed shorted
  • Strain gauge failed shorted
  • Dummy gauge failed shorted
  • Voltage source dead

Answer:

  • Resistor R1 failed open – Possible
  • Resistor R1 failed shorted – Not possible
  • Resistor R2 failed open – Not possible
  • Resistor R2 failed shorted – Possible
  • Strain gauge (measurement) failed open – Not possible
  • Strain gauge (measurement) failed shorted – Possible
  • “Dummy” gauge (temperature compensation) failed open – Possible
  • “Dummy” gauge (temperature compensation) failed shorted – Not possible
  • Voltage source is dead (no voltage output at all) – Not possible

Questions For You:

1. Identify which fundamental principles of electric circuits apply to each step of your analysis of this circuit. In other words, be prepared to explain the reason(s) “why” for every step of your analysis, rather than merely describing those steps.

2. Explain why the two strain gauge elements are orthogonally bonded (i.e. attached 90o to each other) to the specimen.

Share your answers with us through below comments section.

Read Next:

  • Temperature Detectors
  • Strain Gauge Load Cell
  • Parallel Short Circuit Faults
  • Level Switch Control Logic
  • Strain Gauge Accelerometer

Credits: Tony Kuphaldt

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Hydrostatic Level Transmitter Questions
Programmable Logic Controller (PLC) Questions and Answers – 11
Displacer Level Transmitter Questions
Displacer Level Transmitter 5-point Calibration
Investigate High Level Alarm of Distillation Process
Float-type Level Switch to Control a pump
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Questions on Dip Tube Type Level System
Calculate the Magnitude of Hydrostatic Pressure
Surface-mounted Water Pump
Identify High and Low Ports on Pneumatic DP Transmitter
Programmable Logic Controller (PLC) Questions and Answers – 4
Question on Analytical Controller
PLC Practice Questions
Solenoid Valves Practical Problems

Keep Learning

Allen-Bradley MicroLogix 1000 controller

PLC Switch Actuation Status

level control system

Practical Process Control System Questions & Answers – 10

Span of Pressure Gauge

How to Decrease Span of Pressure Gauge?

Manometer Measures Differential Pressure

How Manometer Measures Differential Pressure for Different Fluids?

Calculate Hydraulic System Fluid Pressure

Calculate Hydraulic System Fluid Pressure

Calculate Amount of Weight Indicated by the Scale

Calculate Amount of Weight Indicated by the Scale

Programmable Logic Controller (PLC) Questions and Answers

Programmable Logic Controller (PLC) Questions and Answers – 1

Practical Level Sensors Questions and Answers

Practical Level Sensors Questions and Answers

Learn More

BUS TIE REACTORS

Current Limiting Reactors in Power System

half-wave-voltage-doubler-using-diodes

Half Wave Voltage Doubler using Diodes

Beam Balance Systems Objective Questions

Beam Balance Systems Objective Questions

Cold Email Deliverability

Cold Email Deliverability – Latest Comprehensive Guide

Atomic Absorption Spectroscopy Questions & Answers

Atomic Absorption Spectroscopy Questions & Answers

Difference Between MCB and MCCB

Difference Between MCB and MCCB

Functional Testing of Control Valve Positioners

Functional Testing of Control Valve Positioners