How 3 Wire RTD Lead Wire Resistance Eliminated?

Today i am sharing an article about how a 3 wire RTD eliminates/reduces the lead wire resistance when compared with 2 wire RTD. Also, we will discuss impact of the ambient temperature on RTD measurement.

The following question gives us the clarity about 3 wire RTD and the impact of ambient temperature on RTD temperature measurement.

A Wheatstone bridge, with fixed resistors R1, R2 and R3, of 100 Ω and supplied from a 10 V battery, is used to measure a temperature of 100 °C with a platinum resistance RT, that has a resistance of 139.1 Ω at 100 °C .

The thermometer is connected to the bridge with lead wires that have a resistance Rlead of 10 Ω at 20 °C and the thermometer is correctly calibrated for an ambient temperature of 20 °C.

Assume that the lead resistance changes to 11 Ω when the ambient temperature rises to 30 °C.

Calculate the temperature error introduced at an ambient temperature of 30 °C, when using

a) the two wire method and

b) the three wire method.

We know about RTD Resistance (RT) and bridge resistors values. Calculate I1, I2 and then bridge voltage. The bridge voltage will be used to find-out the equivalent temperature. So measure the bridge voltage for same scenarios with 2 wire & 3 wire RTD at different ambient temperatures and compare them.

2 Wire RTD

RTD Measuring with two leadsTherefore, if the bridge was correctly calibrated for an ambient temperature of 20°C, an error of 0.029 V will occur when the ambient temperature rises to 30 °C.

So instead of reading 100 °C, it would measure approximately 105 °C, an error of 5 °C or 5%.

3 Wire RTD

Therefore, measuring with the three wire method, an error of only 0.006 V will occur. If the thermometer (RTD) was correctly calibrated to read 100 °C at an ambient temperature of 20 °C, then if the ambient temperature rises to 30 °C, the reading of 0.749 V would correspond to a value of 138.76 Ω for RT with no rise in ambient temperature, or in terms of temperature, 99.13 °C, an error of 0.87 °C or 0.87%. This is clearly a remarkable improvement over the two wire method.

So generally we prefer 3 wire RTD instead of 2 wire. We use 4 wire RTD for more accurate temperature measurements (rarely used).

Also Read: How a 4 Wire RTD Works ?

You've successfully subscribed !

View Comments

  • Hi Bharadwaj,
    Can you pls clarify me, in above 2 wire method example, how 1.17V equal to 105deg C of RTD ohms value..? Also in 3 wire method how 0.748V equal to 99.13 degC and how 0.749 V would correspond to a value of 138.76 Ω for RT. Thanks..

Share

Recent Articles

  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

2 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

4 weeks ago
  • PLC Tutorials

PLC Programming Example on Timers Function Block

In this article, you will learn the PLC programming example on timers function block using…

2 weeks ago
  • PLC Tutorials

PLC Pump Control: 10 seconds ON & 20 seconds OFF

Design a program for PLC pump control such that the pump must be turned ON…

2 weeks ago
  • Common

Polyvinyl Alcohol in Oil Field

Polyvinyl alcohol (PVA) is a water-soluble and biodegradable synthetic polymer used in oil field cementing…

1 day ago
  • PLC Tutorials

Electrical Ladder Diagram Control using Timers Example

In this example program, you will learn the electrical ladder diagram control using timers and…

2 weeks ago